background image

CyberOne EC DX IOM Manual 

 

 

 

2.5.4

 

Remote Water Detector  

The remote water detector is normally placed on the sub-floor 
or in a field supplied auxiliary drain pan located beneath the 
unit. STULZ provides two types of water detectors:

 

Spot type water detector-

 

Remove the protective cover and 
connect two control wires to  the 
terminals on the base (terminal 
lugs are provided). Replace the 
cover and place the  water 
detector(s) on the floor with the 
metal electrodes facing down. 
When water is present, current 
will flow  between the electrodes. 
The base is provided with a mounting hole in the center 
which may be used to secure the water detector in place. 

NOTE

 

Do not place the spot type water detector on an 
electrically conductive surface.

 

Cable type water detector-

 

Lay the cable water detector flat across the sub-floor where 
water could collect. When

 

water  is  present,  current  will 
flow between the two wires. A 
two conductor wire harness is 
provided with a quick connect

 

fitting on the end. The harness mates to the fitting on the 
water detector cable and connects it to the terminal block 
inside the electric box.

 

2.5.5

 

Plenum Box Assembly 

If an optional plenum box (plenum extension box or 2-  or 
3-way air distribution plenum box) is selected it is typically 
shipped loose. To install a plenum box, first apply a strip of 
sealing foam around the top flange of the A/C unit or, run a 
bead of silicone sealant. Place the plenum assembly on top 
of  the  unit  as  shown  in  Figure  6 on page  9.  Attach  the 
plenum with the self-tapping screws provided. Holes are 
pre-drilled in the unit and the plenum box. If mounting a 2- or 
3-way air distribution plenum box, the grilles may be removed 
for access to the mounting holes.

 

 

2.6

 

Piping Connections

 

For downflow models, piping is to be routed through the bottom 
of  the  cabinet.  For  upflow  models,  the  piping  is  to  be routed 
through the top of the cabinet. If an optional plenum box is 
installed, drill holes in the top or in the side of the box,  as 
preferred, to route the piping out. Once the piping is completed to 
the A/C unit, install 2-piece pipe penetration plates (shipped 
loose) around the piping to stop air bypass. Mounting holes are 
pre-drilled in the plates. Self-drilling  screws  are  provided  to 

attach  the  plates  to  the  A/C  cabinet. Ensure the space 
between the plates and the pipes are adequately sealed to 
prevent leakage.

 

2.6.1

 

Refrigerant Piping

 

2.6.1.1

 

Self-Contained Systems

 

No refrigerant connections are required for self-contained 
water or glycol-cooled systems (Models COS-024/120- 
W/G-( )).

 

2.6.1.2

 

Split Systems

 

Split air-cooled systems with a remote condenser or remote 
condensing unit will require field installed refrigerant piping. 
All split systems are shipped with a dry nitrogen charge of 

100 psig. Release the pressure via an available stem valve or 
Schrader valve prior to uncapping the pipes. Do not release 
the pressure until the field installed refrigerant piping is ready 
to connect.

 

Upflow units are stubbed inside the cabinet for connecting 
to the condenser. Upflow modes are stubbed outside of 
the cabinet for connecting to the condenser.  The pipe 

stubs are labeled; i.e. Discharge, Suction, Liquid Line. Split 
systems coupled with a remote condenser will require a 
copp

er liquid line and discharge line. Systems utilizing a 

remote condensing unit will require a copper liquid line and 
suction line.

 

The following instructions should be followed to ensure 
proper installation:

 

1.

 

Loosen the two clamps located on the bracket in the 
floor of the cabinet. Run the refrigerant lines through the 
openings in the cabinet and then secure them with the 
clamps. The clamps are labeled; i.e. “Discharge”, “Suc- 
tion”, “Liquid Line” to indicate which line it secures.

 

2.

 

Measure the distance to the refrigerant lines in the cabi- 
net. Mark each pipe and cut to length.

 

3.

 

Join the piping together. Tighten the clamps after the 
pipes are brazed.

 

All  refrigeration piping should be  installed  with  high 
temperature brazed joints. Use  standard  refrigeration 
practices for piping supports, leak testing, dehydration and 
charging of the refrigeration circuits. The refrigeration piping 
should be isolated from the building by the use of vibration 
isolating supports. Provide  supports  (clamps or hangers) 
as necessary every 5 to 10 ft along piping runs to minimize 

vibration and noise transmission. To prevent tube damage 
when  sealing openings in  walls and to  reduce  vibration 
transmission, use a soft flexible material to pack around the 
tubes.

 

Oil traps must be included every 20 ft in the vertical risers and 
the refrigerant lines must be sloped ¼ in. for every 10 ft in the 
horizontal lines to ensure proper oil return to the compressor.

 

13 

Summary of Contents for CyberOne EC DX

Page 1: ...on Operation and Maintenance Manual Chilled Water Systems 12 35 kW Systems Vertical Floor Mounted 60 Hz Data CyberOne EC DX Installation Operation and Maintenance Manual Perimeter Precision Air Condit...

Page 2: ...Systems Inc STULZ This document contains con dential and proprietary information of STULZ Air Technology Systems Inc Distributing or photocopying this document for external distribution is in direct...

Page 3: ...ping 13 2 6 1 1 Self Contained Systems 13 2 6 1 2 Split Systems 13 2 6 1 3 Remote Air CooledCondensers AR 15 2 6 1 4 Remote AirCooled Condensing Units AHU 15 2 6 2 Water Glycol 15 2 6 3 Condensate Dra...

Page 4: ...2 4 1 1 5 Heat Reheat 32 4 1 1 6 Humidi er 32 4 1 1 7 Condensate Pump 33 4 1 2 Condenser 33 4 2 Troubleshooting 33 4 3 Field Service 38 4 3 1 Leak Detection 38 4 3 2 Leak Repair 38 4 3 3 Refrigerant P...

Page 5: ...U Air Handling Unit AR Air Cooled Remote Split G Glycol Cooled RCU O Outdoor Propeller Remote Condensing Unit RCU I Indoor Centrifugal Remote Condensing Unit S Single Pump AWS Alternate Water Source F...

Page 6: ...con gurations The cooling capacity will depend on the unit size which can range from 24 000 to 120 000 BTU H CyberOne EC systems are designed to operate with R407C refrigerant Refer to the unit namep...

Page 7: ...all jewelry watches rings etc Hazardous voltage will still be present inside the electric box at the motor start protectors and circuit breakers even with the unit turned off at the microprocessor co...

Page 8: ...ased water conditioning additives in condensate drain pans Thiswill cause corrosion to occur on the coil ns 1 4 General Design The CyberOne EC DX system is housed in a steel frame type cabinet and is...

Page 9: ...ELECTRIC BOX HEATER EC FAN Figure 1 Typical Internal Layout Down ow Con guration Model COS 024 060 Shown for Reference Figure 2 Typical Internal Layout Up ow Con guration Model COS 096 120 Shown for R...

Page 10: ...icallystops andanalarm is signaled a Locked rotor1 b Loss of a phase1 c Low main supplyvoltage2 d Over heating of electronics2 e Over heating of motor2 1 Upon correction ofthese failure conditions the...

Page 11: ...justable set point Thefree cooling controlvalve opens proportionallyto the demand for cooling basedonthereturnairtemperature sdeviationfromsetpoint Ifthereturnairtemperaturecontinuestorise thefree coo...

Page 12: ...thecompressor turns onandthe AWS control valve closes shuttingoffthe owofchilledwater intothe AWScoolingcoil AWScoolingremains disabled andthe compressor runs until the cut out set point temperature...

Page 13: ...ach side In order to have full service access to internal components no permanent obstructions should be placed in front of the unit See Figure 5 for the minimum recommended front installation clearan...

Page 14: ...usedto minimizeleakage Outsideor freshairshouldbekepttoaminimum asitaddstothecooling heating dehumidification and humidifying loads while maintaining the requirement of the Indoor Air Quality IAQ stan...

Page 15: ...orto match the blower discharge opening s and cut out the holes required for piping and wiring through the raised oor NOTE The equipment must be level to operate properly 2 3 2 Outdoor Equipment Remot...

Page 16: ...unit the conditioned supply air has two methods of discharge Ducted or through a 2 or 3 way grilled plenum box see Figure 8 There are two basic air patterns Frontfreereturnandrearductedreturn If ductw...

Page 17: ...r to the system drawings and supplemental controller manual sent in the data package with your unit 2 5 3 Remote Temperature Humidity Sensor The remote temperature humidity T H sensor must be locateds...

Page 18: ...tach the plates to the A C cabinet Ensure the space between the plates and the pipes are adequately sealed to preventleakage 2 6 1 Refrigerant Piping 2 6 1 1 Self Contained Systems No refrigerant conn...

Page 19: ...2 6 0 1 0 0 5 0 8 2 5 7 8 15 8 0 1 5 0 7 1 0 3 5 1 1 8 22 12 1 8 0 9 1 5 4 5 1 3 8 28 15 2 4 1 2 1 8 6 0 1 5 8 35 17 2 8 1 4 2 0 7 0 2 1 8 45 22 3 9 1 8 3 0 10 2 5 8 51 26 4 6 2 2 3 5 12 3 1 8 65 34 5...

Page 20: ...micalCo Useonlyethyleneglycol with inhibitors for corrosionprotection WARNING Glycol is hazardous Consult the manufacturer s SDS for detailed safetyinformation CAUTIONS After the interconnecting pipin...

Page 21: ...holes for connection of the field wiring conduits These pilot holes are located on the CyberOne EC unit based on the con guration Onan up ow con guration the pilot holes are located inthetop of thecab...

Page 22: ...s within the range of 277V plus 5 the control transformers within the system must have the primary wire connected to its respective 240V tap instead of the 208Vtap Upon examination of the buck boost t...

Page 23: ...th the shield being terminated at the unit electric box The number of conductors needed depends on which system controller is utilized For systems utilizing the model E controller three control conduc...

Page 24: ...control wiring may be installed for the system controller to enable condenser operation only when the compressor is running You must remove the jumper from the remote condenser terminal board see the...

Page 25: ...age electrical box Refer to the electrical drawing supplied with your unit for the number of eldwiresneededandappropriatewireterminationsrequired speci cally for yoursystem Figure 14 Interconnecting F...

Page 26: ...Figure 15 Interconnecting Field Wiring Glycol Systems 21 COS 024 060 G U SHOWN FOR REFERENCE NOTES 1 PHANTOM WIRES NOT APPLICABLE FOR SINGLE PHASE POWER SUPPLIES 2 NUMBER OF CONDUCTORS VARY DEPENDING...

Page 27: ...ing pressures vary depending on the type of refrigerant used in the unit Before charging check the unit nameplate to con rm the type of refrigerant to use Tables are provided in Section 2 8 8 showing...

Page 28: ...r for HGRHand HGBP 3 2 lb Estimated Refrigerant Charge 22 226 lb 2 8 6 Preparing System for Charging 1 With all the system piping connections made perform a dry nitrogen leak detection test on the sys...

Page 29: ...itial vacuum release the vacuum and pressurize the system with 2 3 lbs of drynitrogen Allowthesystemtostandfortwohourswith the dry nitrogen charge This gives time for the nitrogen moleculestodispersei...

Page 30: ...erature reading near the feeler bulbfromthethermalexpansionvalvewiththetempera ture measuring device being well insulated The ideal superheattemperatureis12 15 F Maximumallowable superheat temperature...

Page 31: ...Design Condensing Temp 95 F Ambient 125 105 140 Suction Pressure psig R407C 70 55 85 Fan Cycling Control Fan On psig R407C 320 240 340 Fan Speed Control psig R407C 320 Flooded HP Control Valve psig R...

Page 32: ...or control is used to maintain head pressure The variable speed motor is located closest to the header end of the condenser The fan speed control is a continual modulation of the motor s speed The con...

Page 33: ...h 10 VDC corresponding to the valve opening 100 Thesystemcontrollerisfactorysetforthecorrectcondensing pressure however it can be adjustedto increase ordecrease thecondensingpressure Adjustmentismadeb...

Page 34: ...llen wrench turn clockwise to increase pressure or counterclockwise to lower pressure 3 2 1 1 Full Floating A full oating hot gas bypass system is provided for split AHU Remote Condensing Units The fu...

Page 35: ...peration and Maintenance manual for the humidi er is provided with your unit under separate cover Refer to that manual for detailed information on the humidi er operation 7 Test dehumidi cation operat...

Page 36: ...eavailableandthat allcylinderstobeusedaredesignatedfortherecovered refrigerant and labelled for that refrigerant i e special cylindersforthe recoveryofrefrigerant Cylinders must be complete with press...

Page 37: ...a lowrefrigerant charge ora clogged lter drier Check for humidity in the refrigerant by viewing the color of the indicator in the center of the sight glass and comparing it to the color scale on the...

Page 38: ...oil cleaner Check for bent or damaged coil ns and repair as necessary On outdoor units in winter do not permit snowto accumulate on or aroundthe condensing unit Check all refrigerant lines and capilla...

Page 39: ...ator blower b Temperature setting too low Increase temperature setpoint 68 Fmin c Discharge air short cycling back to return Check discharge grilleorientation d Low refrigerant charge Find leak repair...

Page 40: ...Condenser air intakeis blocked Remove debris and clean condenser c Overcharge ofrefrigerant Reclaim excess refrigerant fromsystem d Lowwater glycol owto water cooled condenser Reset determine cause an...

Page 41: ...ck condenser for obstructions e Minimum off time hasnot expired Wait for time toexpire System Short of Capacity a Low refrigerant indicated by bubblesin sight glass b Expansion valve stuck or obstruct...

Page 42: ...lement Humidi er Inoperative a Water supplyhas been turned offor not connected Connect and or turn on water supply Note See humidifier manual for additional help b Humidi er switch is in Off position...

Page 43: ...are providedto protect the compressor fromfailing If a compressor failure has occurred determine whether it is an electrical or a mechanical failure An electrical failure will beindicatedbythedistinc...

Page 44: ...one size larger than the normal selection size 6 Checktheexpansionvalve sightglassandothercontrols to see if cleaning or replacement isrequired 7 Evacuatethesystemaccordingtostandardprocedures Normall...

Page 45: ...the A C unit On by pressing the Enterkey 8 Readjust the humidity to the desired setpoint If the humidi er is to be shut down for an extended period follow the steps of the Extended Shutdown procedure...

Page 46: ...UPS groundthecustomerisresponsiblefortheshipping charges If you do not have established credit with STULZ you must give a freight carrier accountnumber A written or faxed purchase order is required o...

Page 47: ...valve 9 Humidifier On Off Drain switch is in the on position 10 Filter s installed 11 Duct plenums sealed 12 Incoming line voltage matches equipment nominal nameplated rating tolerances 13 Main power...

Page 48: ...ndensate pan safety switch operates freely Additional Check chilled water hot water circuits for air bleed as required Coils clean and clear of obstructions Humidifier cylinder and controls operate pr...

Page 49: ...upport call 888 529 1266 or email stulztechnicalsupport stulz ats com Support is available 24 7 365 Provide the model number serial number and STULZ item number from the unit nameplate This will speed...

Page 50: ...DF Downflow NFPA National Fire Protection Agency EC Electronically Commutated PH Phase DP Dewpoint PSI Pounds Per Square Inch DX Direct Expansion PSIG Pounds Per Square Inch Gauge ESD Electrostatic D...

Page 51: ...Air Technology Systems Inc 1572 Tilco Drive Frederick MD 21704 301 620 2033 Fax 301 662 5487 info stulz ats com Technical Support 888 529 1266 www stulz usa com OCC0096A Feb 2020 STULZ Air Technology...

Reviews: