background image

CyberOne EC DX IOM Manual 

 

 

 

4.3

 

Field Service

 

NOTE

 

Do not attempt to make repairs without the proper 
tools.

 

It may be necessary to perform repairs on the refrigeration 
system. If field repairs are necessary, the following procedures 
apply:

 

WARNING 

 

 

If refrigerant gas is released in an enclosed area it 
will displace oxygen and act as a suffocant. Always 
ensure adequate ventilation during refrigeration 
repairs.

 

4.3.1

 

Leak Detection

 

Several methods can  be  used  to  detect  a  leak  in  the 
refrigeration system. The most modern and easiest method is 
to use an electronic leak detector. Follow the manufacturer’s 
directions and any leak can be quickly located. A second 
method is to use soap bubbles. Apply a solution of soapy 
water with a brush or sponge to the joints and connections 
in the refrigeration lines. A leak in the lines will cause bubbles 
to form.

 

4.3.2

 

Leak Repair

 

When  a  leak  is  located,  properly reclaim the remaining 
refrigerant charge before beginning repairs. Adjacent piping 
must be thoroughly cleaned by removing all paint, dirt and oily 

film.  Use  a wire  brush, sand  cloth  or sandpaper and wipe 
the area clean  before attempting repair. Protect nearby 
parts from heat damage by wrapping with water-soaked 
cloths.

 

4.3.3

 

Refrigerant Piping

 

When replacing refrigeration components, the following 
consumable materials are recommended:

 

For R407C repairs use Silfos alloy for copper-to-copper 
(piping liquid line or suction line repairs). Silver solder (Safety- 
Silv #45) and flux are to be used on copper-to-brass or 
copper-to-steel repairs.

 

Wrap wet rags around the pipes between the areas to be 
brazed  and any nearby refrigeration components to keep 
excessive heat from traveling through the pipe and causing 
damage.

 

When component replacement is complete, remove all traces of 
flux. After any repair, pressure check the system to ensure there 
are no leaks prior to recharging the system.

 

4.3.4

 

General Common 

Repairs/Component Replacement

 

4.3.4.1

 

Compressor Failure

 

The compressor is the most important component of the air 
conditioner. Numerous safety devices are provided to protect 
the compressor from failing.

 

If a compressor failure has occurred, determine whether it is 
an electrical or a mechanical failure. An electrical failure will 

be indicated by the distinct pungent odor once the system has 
been opened. If a burnout has occurred, the oil will be black 
and acidic. A mechanical failure will have no burned odor and 
the motor will attempt to run, an abnormal or excessive noise 
may be present.

 

An analysis of the oil is the only way to determine the proper 
procedure for cleaning the refrigerant system. Acid test kits 
are available from several manufacturers for measuring the 

acid level in the oil. These are capable of making accurate acid 
measurements, but if they are not available, a check of the oil 
by sight and smell can give a quick indication if contamination 
remains in the system. Since refrigeration oils vary in color, a 
sample of the new oil in the replacement compressor should 
be removed prior to installation and sealed in a small glass 
bottle for comparison purposes. If the oil has been exposed 
to refrigerant, the bottle should not be tightly capped, since 
the residual refrigerant may create a high pressure if tightly 
sealed and exposed to high temperature.

 

CAUTION

 

 

Avoid touching or contacting the gas and oil with 
exposed skin. Severe burns will result. Use long 
rubber gloves in handling contaminated parts.

 

All  electrical connections should be  checked  to  ensure 
they are tight and properly made. Check all circuit breakers, 
contactors and wiring. The contactors should be examined 
and replaced if contacts are worn or pitted.

 

If there is acid in the oil, there has been an electrical failure 
which has caused the compressor motor to burn out. The acid 
diffuses throughout the refrigeration system and must be 
removed by using a burnout filter kit before a new compressor 
is  placed  in  service.  Not  only must the compressor  be 

replaced, but also the entire refrigeration circuit must be 
cleaned of the harmful contaminants left by the burnout. See 
“4.3.4.3 Burn-Out/Acidic Cleanup Procedure” on page 39 
for the proper procedure.

 

If there is no acid in the oil, there has been a mechanical failure. 
See “4.3.4.2 Standard Cleanout Procedure” on page 39 
(Standard Cleanout) for the proper cleaning procedure.

 

 
 

 

38 

Summary of Contents for CyberOne EC DX

Page 1: ...on Operation and Maintenance Manual Chilled Water Systems 12 35 kW Systems Vertical Floor Mounted 60 Hz Data CyberOne EC DX Installation Operation and Maintenance Manual Perimeter Precision Air Condit...

Page 2: ...Systems Inc STULZ This document contains con dential and proprietary information of STULZ Air Technology Systems Inc Distributing or photocopying this document for external distribution is in direct...

Page 3: ...ping 13 2 6 1 1 Self Contained Systems 13 2 6 1 2 Split Systems 13 2 6 1 3 Remote Air CooledCondensers AR 15 2 6 1 4 Remote AirCooled Condensing Units AHU 15 2 6 2 Water Glycol 15 2 6 3 Condensate Dra...

Page 4: ...2 4 1 1 5 Heat Reheat 32 4 1 1 6 Humidi er 32 4 1 1 7 Condensate Pump 33 4 1 2 Condenser 33 4 2 Troubleshooting 33 4 3 Field Service 38 4 3 1 Leak Detection 38 4 3 2 Leak Repair 38 4 3 3 Refrigerant P...

Page 5: ...U Air Handling Unit AR Air Cooled Remote Split G Glycol Cooled RCU O Outdoor Propeller Remote Condensing Unit RCU I Indoor Centrifugal Remote Condensing Unit S Single Pump AWS Alternate Water Source F...

Page 6: ...con gurations The cooling capacity will depend on the unit size which can range from 24 000 to 120 000 BTU H CyberOne EC systems are designed to operate with R407C refrigerant Refer to the unit namep...

Page 7: ...all jewelry watches rings etc Hazardous voltage will still be present inside the electric box at the motor start protectors and circuit breakers even with the unit turned off at the microprocessor co...

Page 8: ...ased water conditioning additives in condensate drain pans Thiswill cause corrosion to occur on the coil ns 1 4 General Design The CyberOne EC DX system is housed in a steel frame type cabinet and is...

Page 9: ...ELECTRIC BOX HEATER EC FAN Figure 1 Typical Internal Layout Down ow Con guration Model COS 024 060 Shown for Reference Figure 2 Typical Internal Layout Up ow Con guration Model COS 096 120 Shown for R...

Page 10: ...icallystops andanalarm is signaled a Locked rotor1 b Loss of a phase1 c Low main supplyvoltage2 d Over heating of electronics2 e Over heating of motor2 1 Upon correction ofthese failure conditions the...

Page 11: ...justable set point Thefree cooling controlvalve opens proportionallyto the demand for cooling basedonthereturnairtemperature sdeviationfromsetpoint Ifthereturnairtemperaturecontinuestorise thefree coo...

Page 12: ...thecompressor turns onandthe AWS control valve closes shuttingoffthe owofchilledwater intothe AWScoolingcoil AWScoolingremains disabled andthe compressor runs until the cut out set point temperature...

Page 13: ...ach side In order to have full service access to internal components no permanent obstructions should be placed in front of the unit See Figure 5 for the minimum recommended front installation clearan...

Page 14: ...usedto minimizeleakage Outsideor freshairshouldbekepttoaminimum asitaddstothecooling heating dehumidification and humidifying loads while maintaining the requirement of the Indoor Air Quality IAQ stan...

Page 15: ...orto match the blower discharge opening s and cut out the holes required for piping and wiring through the raised oor NOTE The equipment must be level to operate properly 2 3 2 Outdoor Equipment Remot...

Page 16: ...unit the conditioned supply air has two methods of discharge Ducted or through a 2 or 3 way grilled plenum box see Figure 8 There are two basic air patterns Frontfreereturnandrearductedreturn If ductw...

Page 17: ...r to the system drawings and supplemental controller manual sent in the data package with your unit 2 5 3 Remote Temperature Humidity Sensor The remote temperature humidity T H sensor must be locateds...

Page 18: ...tach the plates to the A C cabinet Ensure the space between the plates and the pipes are adequately sealed to preventleakage 2 6 1 Refrigerant Piping 2 6 1 1 Self Contained Systems No refrigerant conn...

Page 19: ...2 6 0 1 0 0 5 0 8 2 5 7 8 15 8 0 1 5 0 7 1 0 3 5 1 1 8 22 12 1 8 0 9 1 5 4 5 1 3 8 28 15 2 4 1 2 1 8 6 0 1 5 8 35 17 2 8 1 4 2 0 7 0 2 1 8 45 22 3 9 1 8 3 0 10 2 5 8 51 26 4 6 2 2 3 5 12 3 1 8 65 34 5...

Page 20: ...micalCo Useonlyethyleneglycol with inhibitors for corrosionprotection WARNING Glycol is hazardous Consult the manufacturer s SDS for detailed safetyinformation CAUTIONS After the interconnecting pipin...

Page 21: ...holes for connection of the field wiring conduits These pilot holes are located on the CyberOne EC unit based on the con guration Onan up ow con guration the pilot holes are located inthetop of thecab...

Page 22: ...s within the range of 277V plus 5 the control transformers within the system must have the primary wire connected to its respective 240V tap instead of the 208Vtap Upon examination of the buck boost t...

Page 23: ...th the shield being terminated at the unit electric box The number of conductors needed depends on which system controller is utilized For systems utilizing the model E controller three control conduc...

Page 24: ...control wiring may be installed for the system controller to enable condenser operation only when the compressor is running You must remove the jumper from the remote condenser terminal board see the...

Page 25: ...age electrical box Refer to the electrical drawing supplied with your unit for the number of eldwiresneededandappropriatewireterminationsrequired speci cally for yoursystem Figure 14 Interconnecting F...

Page 26: ...Figure 15 Interconnecting Field Wiring Glycol Systems 21 COS 024 060 G U SHOWN FOR REFERENCE NOTES 1 PHANTOM WIRES NOT APPLICABLE FOR SINGLE PHASE POWER SUPPLIES 2 NUMBER OF CONDUCTORS VARY DEPENDING...

Page 27: ...ing pressures vary depending on the type of refrigerant used in the unit Before charging check the unit nameplate to con rm the type of refrigerant to use Tables are provided in Section 2 8 8 showing...

Page 28: ...r for HGRHand HGBP 3 2 lb Estimated Refrigerant Charge 22 226 lb 2 8 6 Preparing System for Charging 1 With all the system piping connections made perform a dry nitrogen leak detection test on the sys...

Page 29: ...itial vacuum release the vacuum and pressurize the system with 2 3 lbs of drynitrogen Allowthesystemtostandfortwohourswith the dry nitrogen charge This gives time for the nitrogen moleculestodispersei...

Page 30: ...erature reading near the feeler bulbfromthethermalexpansionvalvewiththetempera ture measuring device being well insulated The ideal superheattemperatureis12 15 F Maximumallowable superheat temperature...

Page 31: ...Design Condensing Temp 95 F Ambient 125 105 140 Suction Pressure psig R407C 70 55 85 Fan Cycling Control Fan On psig R407C 320 240 340 Fan Speed Control psig R407C 320 Flooded HP Control Valve psig R...

Page 32: ...or control is used to maintain head pressure The variable speed motor is located closest to the header end of the condenser The fan speed control is a continual modulation of the motor s speed The con...

Page 33: ...h 10 VDC corresponding to the valve opening 100 Thesystemcontrollerisfactorysetforthecorrectcondensing pressure however it can be adjustedto increase ordecrease thecondensingpressure Adjustmentismadeb...

Page 34: ...llen wrench turn clockwise to increase pressure or counterclockwise to lower pressure 3 2 1 1 Full Floating A full oating hot gas bypass system is provided for split AHU Remote Condensing Units The fu...

Page 35: ...peration and Maintenance manual for the humidi er is provided with your unit under separate cover Refer to that manual for detailed information on the humidi er operation 7 Test dehumidi cation operat...

Page 36: ...eavailableandthat allcylinderstobeusedaredesignatedfortherecovered refrigerant and labelled for that refrigerant i e special cylindersforthe recoveryofrefrigerant Cylinders must be complete with press...

Page 37: ...a lowrefrigerant charge ora clogged lter drier Check for humidity in the refrigerant by viewing the color of the indicator in the center of the sight glass and comparing it to the color scale on the...

Page 38: ...oil cleaner Check for bent or damaged coil ns and repair as necessary On outdoor units in winter do not permit snowto accumulate on or aroundthe condensing unit Check all refrigerant lines and capilla...

Page 39: ...ator blower b Temperature setting too low Increase temperature setpoint 68 Fmin c Discharge air short cycling back to return Check discharge grilleorientation d Low refrigerant charge Find leak repair...

Page 40: ...Condenser air intakeis blocked Remove debris and clean condenser c Overcharge ofrefrigerant Reclaim excess refrigerant fromsystem d Lowwater glycol owto water cooled condenser Reset determine cause an...

Page 41: ...ck condenser for obstructions e Minimum off time hasnot expired Wait for time toexpire System Short of Capacity a Low refrigerant indicated by bubblesin sight glass b Expansion valve stuck or obstruct...

Page 42: ...lement Humidi er Inoperative a Water supplyhas been turned offor not connected Connect and or turn on water supply Note See humidifier manual for additional help b Humidi er switch is in Off position...

Page 43: ...are providedto protect the compressor fromfailing If a compressor failure has occurred determine whether it is an electrical or a mechanical failure An electrical failure will beindicatedbythedistinc...

Page 44: ...one size larger than the normal selection size 6 Checktheexpansionvalve sightglassandothercontrols to see if cleaning or replacement isrequired 7 Evacuatethesystemaccordingtostandardprocedures Normall...

Page 45: ...the A C unit On by pressing the Enterkey 8 Readjust the humidity to the desired setpoint If the humidi er is to be shut down for an extended period follow the steps of the Extended Shutdown procedure...

Page 46: ...UPS groundthecustomerisresponsiblefortheshipping charges If you do not have established credit with STULZ you must give a freight carrier accountnumber A written or faxed purchase order is required o...

Page 47: ...valve 9 Humidifier On Off Drain switch is in the on position 10 Filter s installed 11 Duct plenums sealed 12 Incoming line voltage matches equipment nominal nameplated rating tolerances 13 Main power...

Page 48: ...ndensate pan safety switch operates freely Additional Check chilled water hot water circuits for air bleed as required Coils clean and clear of obstructions Humidifier cylinder and controls operate pr...

Page 49: ...upport call 888 529 1266 or email stulztechnicalsupport stulz ats com Support is available 24 7 365 Provide the model number serial number and STULZ item number from the unit nameplate This will speed...

Page 50: ...DF Downflow NFPA National Fire Protection Agency EC Electronically Commutated PH Phase DP Dewpoint PSI Pounds Per Square Inch DX Direct Expansion PSIG Pounds Per Square Inch Gauge ESD Electrostatic D...

Page 51: ...Air Technology Systems Inc 1572 Tilco Drive Frederick MD 21704 301 620 2033 Fax 301 662 5487 info stulz ats com Technical Support 888 529 1266 www stulz usa com OCC0096A Feb 2020 STULZ Air Technology...

Reviews: