10. Dismantling and disposal
The A/C unit can only be dismantled by qualified specialists.
Switch off the A/C unit at the controller and at the master switch. Switch off power conducting cables to the unit and
secure them against being switched on again. Disconnect the A/C unit from the de-energized network.
Dispose of the refrigerant in the unit in accordance with the disposal and safety regulations applicable on site
The refrigerant may not be discharged into the atmosphere, but must be returned to the manufac-
turer, if it is not reused.
The ester oil in the compressor must also be disposed. As it contains dissolved refrigerant, it can
not be disposed like usual oils, but must be returned to the oil manufacturer.
Disconnect the depressurized refrigerant pipes from the external system (version AS).
If glycol or similar additives had been used, this liquid also has to be collected and disposed in
an appropriate manner and may under no circumstances be introduced in the local waste water
system.
Disconnect the unit from the external water circuit by closing the shut-off valves and drain the water circuit of the
unit (version GS, GES, CW).
Disconnect the depressurized cooling water pipes of the unit from the external system.
Move the unit, as described in the chapter "transport", with a lifting device of sufficient load-carrying capacity.
Dispose of the A/C unit in accordance with the disposal and safety regulations applicable on site. We recommend a
recycling company for this. The unit basically contains the raw materials aluminium (heat exchanger), copper (pipe-
lines, wiring), and iron (condenser, panelling, mounting panel).