P. Plus Menu* config.
EVO Menu* config.
EN
Here the BMS settings must be selected. The serial Modbus address
of the μPC is set on 001 as standard and has not to be changed. In the
C7000IOC however, the command "icc 1 id 1" must be entered to enable
a communication.
The baudrate must be set on 9600.
Here the used compressor must be adjusted. The compressor type can
be seen on the type plate of the compressor.
SIAM ANB33-400V
or
SIAM ANB42-400V
or
SIAM ANB52-400V
(Set default: Yes) By this setting the inverter suitable to the compressor is
initialized suitable. It is compellingly required to select "Yes". Following the
data is written in the inverter.
The program verifies the compatibility of Kcompressor and inverter, dis-
plays the result of the verification in Wz04a and requires the confirmation
for writing the default setting.
Write default: Yes
After the confirmation with the ENTER key, the display shows "Wait de-
fault install", then the value for "Write default" switches back to "No".
By ESC you get back to view Wz04.
Scroll to view Wz08 with the "down arrow" key.
Confirm the configuration with "Yes".
To navigate among the different windows by the arrow keys, the cursor must be in the left top
corner.
Menu structure
On the following pages some set-
tings will be changed in the views
Pc09, Co04, Co05, Co08, Co14,
Co15, Ea02 and Eb02.
The menu structure helps you to
find these windows.