/05.2015/
G35
7
EN
Unit version A/AS: The refrigerant circuit is filled with nitrogene up to atmospheric pressure.
Unit version GS/GES: The refrigerant circuit is filled with refrigerant ready for use.
3. Transport / Storage
3.1 Delivery of units
Stulz A/C units are mounted on pallets and packed several times in plastic film. They must always be transported
upright on the pallets.
When delivery is accepted, the unit is to be checked against the delivery note for completeness
and checked for external damage which is to be recorded on the consignment note in the presence
of the freight forwarder.
•
The delivery note can be found on the A/C unit when delivered.
• The shipment is made ex works, in case of shipment damages, please assert your claim towards
the carrier.
• Hidden damage is to be reported in writing
within 6 days
of delivery.
The following information can be found on the packing.
1) Stulz logo
2) Stulz order number
3) Type of unit
4) Packing piece - contents
5) Warning symbols
also upon request
6) Gross weight
7) Net weight
8) Dimensions
9) Customer order number
10) Additional customer requirements
Construction of protective covering
(from inside to outside)
1. Neopolene cushioning
2. Shrink film
3. Additional board in container shipments
3.2 Transport
The Stulz A/C units can be moved by lifting devices with ropes, for this the ropes have to be fixed at the pallet, and
the upper unit edges have to be protected by wooden laths or metal brackets in such a way that they could not be
caved in.
You can move the unit still packaged on the pallet with a fork lift, if you take care that the centre of gravity is within
the fork surface. Take care that the unit is in an upright position at the transport.
3.3 Storage
If you put the unit into intermediate storage before the installation, the following measures have to be carried out to
protect the unit from damage and corrosion:
• Make sure that the water connections are provided with protective hoods. If the intermediate storage exceeds 2
months, we recommend filling the pipes with nitrogen.
• the temperature at the storage point should not be higher than 42°C, and the site should not be exposed to direct
sunlight.
• the unit should be stored packaged to avoid the risk of corrosion especially of the heat exchanger fins.
Never move the unit on rollers and never transport it without pallet on a fork lift, for the risk of
distorting the frame.