background image

(Mar, 2012)

Compact CWE Series Installation, Operation & Maintenance Manual

Air Technology Systems, Inc.

4.3     Field Service

NOTE

Do not attempt to make repairs without the 
proper tools.

It may be necessary to perform repairs on the A/C 
system. If fi eld repairs are necessary, the following 
procedures apply:

1.  All electrical connections should be checked to 

ensure they are tight and properly made.

2.  Check all circuit breakers, contacts and wiring. 

The contactor should be examined and replaced 
if contacts are worn or pitted.

4.3.1   General Common Repairs/
  

 Component 

Replacement

4.3.1.1     Cooling System

NOTE:  Repairs to refrigeration systems must be 
performed by a journeyman refrigeration mechanic or 
air conditioning technician.

If the Chilled Water system isn’t cooling or if cool-
ing is reduced, check for leaks in the system. Check 
for clogged water lines. If fi lters are installed in the 
CW lines, check the condition of the fi lters. Clean or 
replace the fi lters if necessary.

4.3.1.2   Leaks

A leak in a chilled water cooling system will usually 
form a puddle of fl uid beneath the unit that can 
be easily seen. Visually trace the leak up from the 
puddle to the area on the unit where fl uid may be 
seen dripping.

When a leak is detected, properly reclaim the 
remaining CW coolant before attempting repairs.  
Adjacent piping must be thoroughly cleaned by 
removing all paint, dirt and oily fi lm.  Use wire brush, 
sandcloth or sandpaper and wipe the area with clean, 
dry cloths.  Protect nearby parts from heat damage 
by wrapping with water-soaked cloths.

For copper-to-copper (piping) repairs use SILFOS 
Alloy. No fl ux is required with Silfos Alloy. Silver 
solder (Stay Silv #45) and fl ux are to be used on 
copper-to-brass or copper-to-steel repairs. 

When repairs are completed, remove all traces of 
fl ux. After any repair, pressurize the system to check 
for leaks prior to recharging the system.

4-4

4.3.1.3   Humidifi er Cylinder Replacement

After an extended period of operation, the yellow LED 
on the humidifi er cabinet will repeatedly fl ash four 
times indicating that the cylinder is completely used 
and a replacement cylinder must be installed. The 
cylinder is disposable and cylinder life is dependent 
on water supply conditions and humidifi er usage. 
Refer to the humidifi er operator’s manual supplied 
under separate cover for detailed instructions on 
changing the cylinder. The following procedures are 
to be followed when replacing the cylinder.

CAUTION

 

Failure to replace the cylinder at the end of 
cylinder life may result in humidifi er damage.

NOTE

Decrease the humidity setpoint below ambient 
humidity to allow the cylinder to cool down 
before removing the cylinder.

1.   Turn the A/C unit Off by pressing (and holding) 

the Enter key on the E² controller.

2.   Turn off the water supply to the humidifi er.

3.   Open the door of the A/C unit and turn the main 

power disconnect switch on the electric box Off. 
Remove the cover from the electric box.

4.   Fashion a jumper wire and 

install it across the terminals on 
the Air Flow Switch (F40).

5.   Using a pair of vise grips, turn 

the shaft of the main power 
switch to the On position to 
provide power for the humidifi er 
drain solenoid.

6.   Drain the cylinder by pushing 

the “On-Off-Drain” switch to the 
“Drain” position.

7.   When drained, push the “On-Off-Drain” switch to 

the “Off” position.

8.   Remove the jumper wire from the Air Flow switch 

and turn the main power disconnect switch Off to 
disconnect power from the humidifi er.

9.   The power wires to the cylinder are attached by 

cylinder plugs to the electrode pins on top of the 
cylinder. Pull these plugs vertically off the pins.

CAUTION 

The cylinder and steam hose may be hot and 
burns may result.

Summary of Contents for Compact CWE

Page 1: ...Compact CWE Installation Operation and Maintenance Manual Perimeter Mounted Precision Air Conditioners 30 kW 360 kW 60 Hz...

Page 2: ...CW E UF 0 Number of Refrigeration Circuits Model Nomenclature E EC Fan Electronically Commutated EC Fan Highly reliable EC Fans offer considerable energy cost savings and long life Using an electronic...

Page 3: ...re Humidity Sensor 2 7 2 6 6 1 Types of Control 2 7 2 6 7 Remote Water Detector 2 8 2 7 Piping Connections 2 9 2 7 1 Chilled Water Hot Water 2 9 TABLE OF CONTENTS 2 7 2 Condensate Drain 2 9 2 7 2 1 Gr...

Page 4: ...Checklist A 2 Appendix B Glossary Definition of Terms and Acronyms B 1 Notice This document contains information protected by copyright All rights are reserved The owner of the equipment for which th...

Page 5: ...nt of cooling required The controller modulates the valve opening together with the fan speed to meet the user selectable temperature setpoint Heat from the surrounding air is transferred through the...

Page 6: ...ective for a period of 24 months from the date of start up Parts repaired or replaced under this warranty are shipped FOB factory ground and warranted for the balance of the original warranty period o...

Page 7: ...y placards stickers have been placed on the unit to call attention to all personal and equipment damage hazard areas Never work on electrical equipment unless another person who is familiar with the o...

Page 8: ...ons should be disposed of in accordance with local and state regulatory statutes CAUTION Chilled water cooling coils and associated piping circuits are pressurized up to 100 psi and sealed when they l...

Page 9: ...ncluded to further describe the feature s Figure 1 depicts a sample internal layout of a CCU upflow unit and identifies the major components Location of the major components vary depending on CWE mode...

Page 10: ...a 0 to 10 VDC signal from the system controller The fan motor is equipped with integral electronics and does not require the addition of secondary electronics such as thermal protection inverters or...

Page 11: ...ontroller provides an alarm signal and the alarm display indicates which power source failed When the primary power source is functionally restored the operation of the A C system is automatically tra...

Page 12: ...se such as controllers temperature humidity sensors water detectors etc are shipped inside the air conditioner unless specified otherwise by the customer The plenum box if applicable is shipped separa...

Page 13: ...stallation draw ing The unit is shipped on a skid to facilitate moving prior to installation The unit should always be stored indoors in a dry location prior to installation CAUTION When moving the un...

Page 14: ...ducted or through a 2 or 3 way grilled plenum box see Figure 8 The return air pattern is front free return The supply air outlet is provided with a flange for connecting the ductwork refer to the inst...

Page 15: ...provided with a turned in flange on top of the unit for connection of ductwork refer to the installation drawing provided with the unit The connection of ductwork to the unit may be made with either p...

Page 16: ...emove the shipping support brackets after the A C unit is mounted in it s final location 2 6 Optional Equipment Field Installed NOTE Do not mount any optional equipment on the unit access doors 2 6 1...

Page 17: ...g and raising the fans Hold the fan assembly down so the top plate is on the floor of the cabinet as shown in Figure 12 Align the two holes in each corner of the top plates with the threaded inserts i...

Page 18: ...mount the sensor Temperature Humidity Sensor 1 Remove the cover from the base of the sensor by squeezing it at the top and bottom CAUTION Take care not to damage the exposed tem perature humidity sens...

Page 19: ...sor may be used for supply air control The sensor is field installed in the supply air stream The supply air temperature and humidity are monitored by the system controller and compared to limit value...

Page 20: ...densate drain line 2 7 Piping Connections 2 7 1 Chilled Water Hot Water Pipe connections for the chilled water and optional hot water reheat piping are sweat connections In most cases they terminate i...

Page 21: ...NOTE 2 Figure 16 Condensate Pump If an optional field installed condensate pump is used a p trap must be installed to allow proper condensate drainage see Figure 16 The height of the trap must be a m...

Page 22: ...required WARNING Verify power is turned off before making connections to the equipment NOTE All wiring must conform to local and national electrical code requirements Use of copper conductors only is...

Page 23: ...g 6 Power Switches Motor Starter Protectors Quantity Varies 7 Water Detector Control Module Optional CAUTION Prior to unit operation an adequate unit to earth ground must be connected to the unit 2 8...

Page 24: ...electrical box see Figure 18 If customer furnished the wire insulation must be rated at 600V Refer to the electrical schematic supplied with your unit for proper wire terminations 2 9 System Settings...

Page 25: ...e humidifier Visually check for vapor leaving the steam head or feel if the cylinder is warm to verify if the humidifier is operational In all cases 1 to 6 hours might be required to see a desired lev...

Page 26: ...as automatic controls may start them unexpectedly 4 1 1 Compact CWE Precision A C Unit 4 1 1 1 Air Filter The air filter is usually the most neglected item in an air conditioning system To maintain e...

Page 27: ...10 VDC control signal to the fan s Refer to the electric drawing to determine the correct I O board terminal numbers This must done within 15 seconds of turning the disconnect switch On or the control...

Page 28: ...ped see item immediately above e Heater element burned out Check continuity with an ohmmeter Replace heater element Hot Water Heater a Low hot water flow Check hot water flow at supply source Inoperab...

Page 29: ...s When repairs are completed remove all traces of flux After any repair pressurize the system to check for leaks prior to recharging the system 4 4 4 3 1 3 Humidifier Cylinder Replacement After an ext...

Page 30: ...Push the On Off Drain switch to the On position 17 Replace the cover on the electric box and turn the main power disconnect switch to the On position 18 Turn on the water supply to the humidifier 19 T...

Page 31: ...han UPS ground the customer is responsible for the shipping charges If you do not have established credit with SATS you must give a freight carrier account number A written or faxed purchase order is...

Page 32: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 33: ...y line connected to humidifier If required If shut off valve is installed open valve 9 Safety pan installed under ceiling mounted equipment if required 10 Filter s installed if required 11 Ductwork co...

Page 34: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 35: ...perate Properly Semi Annually Tighten Electrical Connections Clean Unit as Necessary Check Contacts on Contactors Clean Coils for Pitting Clean Condensate Pump Heat Reheat Operational Annually Inspect...

Page 36: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 37: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc NOTES...

Page 38: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 39: ...Load Amps FOB Freight on Board HACR Heating Air Conditioning Refrigeration HP Horse Power Hz Hertz IAQ Indoor Air Quality in w g Inches of Water Gauge kVA Kilo Volt Amps kW Kilowatt MAX CKT BKR Maxim...

Page 40: ...t CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc OZZ0003 Rev E March 2012 Compact CWE Series Installation Operation and Maintenance Specifications are subject to chang...

Reviews: