Compact CWE Series Installation, Operation & Maintenance Manual
Air Technology Systems, Inc.
SYMPTOM PROBABLE
CAUSE
RECOMMENDATION
4-3
EC Fan(s) Fail to Start
After the causes below are corrected,
(Cont.)
the fan(s) must be manually reset by
turning off power for 20 seconds:
4. Over temperature of electronics
5. Over temperature of motor
Control is Erratic
Wiring improperly connected or broken
Check wiring against schematic diagram
System Short of Capacity
a. Low Chilled Water fl ow
Check for leaks. Repair and recharge
system.
b. Supply water temperature too high
Check chilled water supply
c. Reduced airfl ow
Check fi lters
d. Dirty Coil
Clear coil fi ns of debris
Electric Heater
a. Circuit breaker tripped
Check for short circuit; reset circuit
Inoperable
breaker.
b. Temperature setpoint too low
Increase temperature setpoint
c. Overheat switch open
Insuffi cient air fl ow across heater elements.
Check for dirty fi lters or obstructions
that may reduce air fl ow. Correct or
replace as needed.
d. Manual reset overheat safety
Reset manual overheat safety switch
switch tripped
(see item immediately above).
e. Heater element burned out
Check continuity with an ohmmeter
Replace heater element
Hot Water Heater
a. Low hot water fl ow
Check hot water fl ow at supply source.
Inoperable
Inspect piping for leaks or obstructions.
b. Hot water supply temperature too low
Check hot water supply
c. Temperature setpoint too low
Increase temperature setpoint
d. Control power interrupted
Check for loose or broken wires
Humidifi er Inoperable
a. Water supply has been turned
Connect and/or turn on water supply
Note:
See Humidifi er
off or not connected
Manual for Additional Help.
b.
Humidifi er switch is in “Off” position
Turn switch to “Auto/On” position
c. Electrical connections are loose
Tighten electrical connections
d.
Humidifi er circuit breaker tripped
Check for excess current draw by the
humidifi er electrodes. Drain water from tank
and
refi ll. Reset circuit breaker.
e. Relative humidity is above setpoint
Adjust humidity setpoint
f. Electrode canister change cylinder
1. Consult humidifi er manual
light is activated
2. Water conductivity is too low and
water is at the top of the cylinder
(see next item).
g. Water conductivity is too low
Add a teaspoon of table salt to the water
through the top of the cylinder. Typically
only required during initial start-up.