background image

(Mar, 2012)

Compact CWE Series Installation, Operation & Maintenance Manual

Air Technology Systems, Inc.

2-7

2.6.4   Remote Display

As an option, a factory supplied controller display 
may be remotely mounted. For mounting and wiring 
instructions, refer to the system drawings and the 
supplemental manual sent in the data package with 
your unit.

2.6.5   Condensate Pump

An optional, factory installed condensate pump may 
be provided for automatically eliminating condensate 
and humidifi er fl ush water from the drain pan. The 
condensate pump is typically installed by the factory 
inside the A/C unit. If an optional, fi eld installed 
condensate pump is selected, it should be located 
as near as possible to the air conditioning system. 
The pump should be positioned so the inlet hole in 
the pump is below the drain pan inside the A/C unit. 
Secure the pump in place with a mounting clamp or 
use an adhesive that’s appropriate for the mounting 
surface. Ensure that the pump is level for proper 
operation.

2.6.6   Remote Temperature/Humidity Sensor

The remote temperature/humidity (T/H) sensor must 
be located so that it will properly sense the tempera-
ture/humidity conditions to be controlled. Depending 
on the type of control selected (see Section 2.6.6.1), 
the sensor may be factory mounted or shipped loose 
for fi eld installation. The T/H sensor should not be 
mounted near a doorway or an area where it would be 
exposed to direct sunlight. When locating the sensor, 
consider the length of wire to be used. As an option, 
a 75 foot or 150 foot long cable may be provided by 
SATS. Follow the steps below to mount the sensor. 

Temperature /Humidity Sensor

1.  Remove the cover from the base of the sensor 

by squeezing it at the top and bottom.

CAUTION

 

Take care not to damage the exposed tem-
perature/humidity sensors on the PC board 
when the cover is removed. The sensors can 
be damaged if handled improperly.

2.  Place the base temporarily against the mounting 

surface. 

3.   Level the base. Mark and drill mounting holes 

through at least two of the available slotted holes.

4.  Run a 3 conductor shielded cable through the 

opening in the base, then secure the base with 
screws ensuring the word TOP on the PC board 
is oriented upward.

5.  Make the wiring connections. Refer to Section 

2.8, Utility Connections and refer to the wiring 
diagram supplied with your unit. 

6.  Seal the hole in the wall behind the sensor.

7.  Replace the cover plate on the base.

CAUTION

 

The sensor can be damaged if handled 
improperly. Take care not to damage the 
exposed temperature/humidity sensor on the 
PC board. Do not touch the sensor as this will 
affect its accuracy. 

2.6.6.1  Types of control

Room Air Control (standard)- The A/C unit is provided 
with a temperature and humidity (T/H) sensor, factory 
mounted in the return air stream of the A/C unit. The 
return air temperature and humidity are monitored by 
the system controller and compared to limit values 
set at the factory. Control outputs are based on set 
points entered into the system controller by the user.

Figure 15- Temperature/Humidity Sensor Location

HEIGHT > 60"

T/H SENSOR FOR 
RETURN AIR

T/H SENSOR FOR 

ROOM AIR

SUPPLY AIR

T/H SENSOR 

FOR SUPPLY AIR

 

As an alternative to locating the T/H sensor inside 
the A/C unit, it may be fi eld installed under a raised 
fl oor for sensing supply air conditions or, on a wall 
in the conditioned space for sensing actual room 
conditions.  

Summary of Contents for Compact CWE

Page 1: ...Compact CWE Installation Operation and Maintenance Manual Perimeter Mounted Precision Air Conditioners 30 kW 360 kW 60 Hz...

Page 2: ...CW E UF 0 Number of Refrigeration Circuits Model Nomenclature E EC Fan Electronically Commutated EC Fan Highly reliable EC Fans offer considerable energy cost savings and long life Using an electronic...

Page 3: ...re Humidity Sensor 2 7 2 6 6 1 Types of Control 2 7 2 6 7 Remote Water Detector 2 8 2 7 Piping Connections 2 9 2 7 1 Chilled Water Hot Water 2 9 TABLE OF CONTENTS 2 7 2 Condensate Drain 2 9 2 7 2 1 Gr...

Page 4: ...Checklist A 2 Appendix B Glossary Definition of Terms and Acronyms B 1 Notice This document contains information protected by copyright All rights are reserved The owner of the equipment for which th...

Page 5: ...nt of cooling required The controller modulates the valve opening together with the fan speed to meet the user selectable temperature setpoint Heat from the surrounding air is transferred through the...

Page 6: ...ective for a period of 24 months from the date of start up Parts repaired or replaced under this warranty are shipped FOB factory ground and warranted for the balance of the original warranty period o...

Page 7: ...y placards stickers have been placed on the unit to call attention to all personal and equipment damage hazard areas Never work on electrical equipment unless another person who is familiar with the o...

Page 8: ...ons should be disposed of in accordance with local and state regulatory statutes CAUTION Chilled water cooling coils and associated piping circuits are pressurized up to 100 psi and sealed when they l...

Page 9: ...ncluded to further describe the feature s Figure 1 depicts a sample internal layout of a CCU upflow unit and identifies the major components Location of the major components vary depending on CWE mode...

Page 10: ...a 0 to 10 VDC signal from the system controller The fan motor is equipped with integral electronics and does not require the addition of secondary electronics such as thermal protection inverters or...

Page 11: ...ontroller provides an alarm signal and the alarm display indicates which power source failed When the primary power source is functionally restored the operation of the A C system is automatically tra...

Page 12: ...se such as controllers temperature humidity sensors water detectors etc are shipped inside the air conditioner unless specified otherwise by the customer The plenum box if applicable is shipped separa...

Page 13: ...stallation draw ing The unit is shipped on a skid to facilitate moving prior to installation The unit should always be stored indoors in a dry location prior to installation CAUTION When moving the un...

Page 14: ...ducted or through a 2 or 3 way grilled plenum box see Figure 8 The return air pattern is front free return The supply air outlet is provided with a flange for connecting the ductwork refer to the inst...

Page 15: ...provided with a turned in flange on top of the unit for connection of ductwork refer to the installation drawing provided with the unit The connection of ductwork to the unit may be made with either p...

Page 16: ...emove the shipping support brackets after the A C unit is mounted in it s final location 2 6 Optional Equipment Field Installed NOTE Do not mount any optional equipment on the unit access doors 2 6 1...

Page 17: ...g and raising the fans Hold the fan assembly down so the top plate is on the floor of the cabinet as shown in Figure 12 Align the two holes in each corner of the top plates with the threaded inserts i...

Page 18: ...mount the sensor Temperature Humidity Sensor 1 Remove the cover from the base of the sensor by squeezing it at the top and bottom CAUTION Take care not to damage the exposed tem perature humidity sens...

Page 19: ...sor may be used for supply air control The sensor is field installed in the supply air stream The supply air temperature and humidity are monitored by the system controller and compared to limit value...

Page 20: ...densate drain line 2 7 Piping Connections 2 7 1 Chilled Water Hot Water Pipe connections for the chilled water and optional hot water reheat piping are sweat connections In most cases they terminate i...

Page 21: ...NOTE 2 Figure 16 Condensate Pump If an optional field installed condensate pump is used a p trap must be installed to allow proper condensate drainage see Figure 16 The height of the trap must be a m...

Page 22: ...required WARNING Verify power is turned off before making connections to the equipment NOTE All wiring must conform to local and national electrical code requirements Use of copper conductors only is...

Page 23: ...g 6 Power Switches Motor Starter Protectors Quantity Varies 7 Water Detector Control Module Optional CAUTION Prior to unit operation an adequate unit to earth ground must be connected to the unit 2 8...

Page 24: ...electrical box see Figure 18 If customer furnished the wire insulation must be rated at 600V Refer to the electrical schematic supplied with your unit for proper wire terminations 2 9 System Settings...

Page 25: ...e humidifier Visually check for vapor leaving the steam head or feel if the cylinder is warm to verify if the humidifier is operational In all cases 1 to 6 hours might be required to see a desired lev...

Page 26: ...as automatic controls may start them unexpectedly 4 1 1 Compact CWE Precision A C Unit 4 1 1 1 Air Filter The air filter is usually the most neglected item in an air conditioning system To maintain e...

Page 27: ...10 VDC control signal to the fan s Refer to the electric drawing to determine the correct I O board terminal numbers This must done within 15 seconds of turning the disconnect switch On or the control...

Page 28: ...ped see item immediately above e Heater element burned out Check continuity with an ohmmeter Replace heater element Hot Water Heater a Low hot water flow Check hot water flow at supply source Inoperab...

Page 29: ...s When repairs are completed remove all traces of flux After any repair pressurize the system to check for leaks prior to recharging the system 4 4 4 3 1 3 Humidifier Cylinder Replacement After an ext...

Page 30: ...Push the On Off Drain switch to the On position 17 Replace the cover on the electric box and turn the main power disconnect switch to the On position 18 Turn on the water supply to the humidifier 19 T...

Page 31: ...han UPS ground the customer is responsible for the shipping charges If you do not have established credit with SATS you must give a freight carrier account number A written or faxed purchase order is...

Page 32: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 33: ...y line connected to humidifier If required If shut off valve is installed open valve 9 Safety pan installed under ceiling mounted equipment if required 10 Filter s installed if required 11 Ductwork co...

Page 34: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 35: ...perate Properly Semi Annually Tighten Electrical Connections Clean Unit as Necessary Check Contacts on Contactors Clean Coils for Pitting Clean Condensate Pump Heat Reheat Operational Annually Inspect...

Page 36: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 37: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc NOTES...

Page 38: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 39: ...Load Amps FOB Freight on Board HACR Heating Air Conditioning Refrigeration HP Horse Power Hz Hertz IAQ Indoor Air Quality in w g Inches of Water Gauge kVA Kilo Volt Amps kW Kilowatt MAX CKT BKR Maxim...

Page 40: ...t CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc OZZ0003 Rev E March 2012 Compact CWE Series Installation Operation and Maintenance Specifications are subject to chang...

Reviews: