background image

(Mar, 2012)

Compact CWE Series Installation, Operation & Maintenance Manual

Air Technology Systems, Inc.

with your unit. Provide manual shut-off valves in both 
the supply and return lines for servicing the unit and 
for emergency isolation.

NOTE

A 60-mesh strainer is recommended to be 
installed in the supply line. The strainer screen 
should be cleaned periodically.

CAUTION

 

Chilled water cooling coils and associated 
piping circuits are 

pressurized (up to 100 psi)

 

and sealed when the unit leaves the factory. 
Before installing the interconnecting piping, 
release the pressure via an available stem 
valve or schrader valve prior to uncapping the 
pipes.

If newly installed CW supply and return piping is 
used, it is recommended that the piping system be 
cleaned prior to connecting it to the unit. 

If solvents/

cleaning solutions are used, ensure they are 
completely fl ushed from the piping before 
connecting it.

 Failure to do so could result in 

equipment problems

CAUTION

 

When installing and fi lling chilled water and 
optional hot water reheat loops, all air must be 
bled from the piping system.

NOTE

Chilled water lines should be insulated to 
prevent condensation from forming on the pipes 
if ambient dew point temperatures are higher 
than the fl uid temperatures.

2.7.2   Condensate Drain

2.7.2.1   Gravity Drain

A drain line is installed to drain the condensate pan. If 
an optional humidifi er is used, the drain line from the 
humidifi er is typically connected to the condensate 
drain line. The end of the drain line is clamped inside 
the cabinet. The installer must install a customer 
supplied drain hose to the end of the drain line to 
remove water from the cabinet. See the installation 
drawing provided with your unit for the size and 
location of the condensate drain line.

2.7   Piping 

Connections

2.7.1   Chilled Water/Hot Water

Pipe connections for the chilled water and optional 
hot water reheat piping are sweat connections. In 
most cases, they terminate inside the cabinet except 
units which are provided with pipe connections 
protruding through the top of the cabinet. 

When considering how to route the piping and wiring 
for CCU (upfl ow) units furnished without top piping, 
entry holes may be drilled through either the fl oor 
of the cabinet or through a side panel. The SATS 
installation drawing (furnished with your unit) shows 
a recommended entry location. For special piping 
requirements contact SATS for technical assistance.

For CCD (downfl ow) units, open areas for routing 
the piping and wiring are available in the base of the 
cabinet. Refer to the installation drawing provided 
with your unit for the location of the openings. 

If piping is brought into the side of the cabinet, ensure 
adequate working space is available on that side or 
if necessary cut a service opening into the adjacent 
wall if the unit is installed in a corner. After the piping 
is installed, seal the gaps between the pipes and the 
entrance holes so air won’t leak around the pipes.

For pipe connection sizes, refer to the following table:

 

INLET/OUTLET PIPE SIZES

 

 

Chilled Water     Hot Water

Model # 

     (Inches O.D.)

 

     (Inches O.D.)

CCU/D-300 

       1 1/8” 

         7/8”

CCU/D-600 

       1 5/8” 

         7/8”

CCU/D-900 

       1 5/8” 

         7/8”

CCU/D-1200 

       2 1/8” 

         7/8”

CCU/D-1800 

       2 1/8” 

         7/8”

CCU/D-2300 2 

1/8” (*or 2 5/8)           7/8”

CCU/D-2800 2 

1/8” (*or 2 5/8)           7/8”

CCU/D-3600 

    

      

3”           

         7/8”

 

*Special models requiring high CW fl ow are equipped with 2 5/8”.

Field piping is not necessarily the same size as the 
units’ pipe connections. Piping should be sized to 
match the system pressure drop and fl ow capacity, 
and may require reducing fi ttings to match the 
connection size on the air conditioner. An air vent and 
several schrader valves are installed in the precision 
A/C unit piping.

 

Refer to the piping diagram supplied 

2-9

Summary of Contents for Compact CWE

Page 1: ...Compact CWE Installation Operation and Maintenance Manual Perimeter Mounted Precision Air Conditioners 30 kW 360 kW 60 Hz...

Page 2: ...CW E UF 0 Number of Refrigeration Circuits Model Nomenclature E EC Fan Electronically Commutated EC Fan Highly reliable EC Fans offer considerable energy cost savings and long life Using an electronic...

Page 3: ...re Humidity Sensor 2 7 2 6 6 1 Types of Control 2 7 2 6 7 Remote Water Detector 2 8 2 7 Piping Connections 2 9 2 7 1 Chilled Water Hot Water 2 9 TABLE OF CONTENTS 2 7 2 Condensate Drain 2 9 2 7 2 1 Gr...

Page 4: ...Checklist A 2 Appendix B Glossary Definition of Terms and Acronyms B 1 Notice This document contains information protected by copyright All rights are reserved The owner of the equipment for which th...

Page 5: ...nt of cooling required The controller modulates the valve opening together with the fan speed to meet the user selectable temperature setpoint Heat from the surrounding air is transferred through the...

Page 6: ...ective for a period of 24 months from the date of start up Parts repaired or replaced under this warranty are shipped FOB factory ground and warranted for the balance of the original warranty period o...

Page 7: ...y placards stickers have been placed on the unit to call attention to all personal and equipment damage hazard areas Never work on electrical equipment unless another person who is familiar with the o...

Page 8: ...ons should be disposed of in accordance with local and state regulatory statutes CAUTION Chilled water cooling coils and associated piping circuits are pressurized up to 100 psi and sealed when they l...

Page 9: ...ncluded to further describe the feature s Figure 1 depicts a sample internal layout of a CCU upflow unit and identifies the major components Location of the major components vary depending on CWE mode...

Page 10: ...a 0 to 10 VDC signal from the system controller The fan motor is equipped with integral electronics and does not require the addition of secondary electronics such as thermal protection inverters or...

Page 11: ...ontroller provides an alarm signal and the alarm display indicates which power source failed When the primary power source is functionally restored the operation of the A C system is automatically tra...

Page 12: ...se such as controllers temperature humidity sensors water detectors etc are shipped inside the air conditioner unless specified otherwise by the customer The plenum box if applicable is shipped separa...

Page 13: ...stallation draw ing The unit is shipped on a skid to facilitate moving prior to installation The unit should always be stored indoors in a dry location prior to installation CAUTION When moving the un...

Page 14: ...ducted or through a 2 or 3 way grilled plenum box see Figure 8 The return air pattern is front free return The supply air outlet is provided with a flange for connecting the ductwork refer to the inst...

Page 15: ...provided with a turned in flange on top of the unit for connection of ductwork refer to the installation drawing provided with the unit The connection of ductwork to the unit may be made with either p...

Page 16: ...emove the shipping support brackets after the A C unit is mounted in it s final location 2 6 Optional Equipment Field Installed NOTE Do not mount any optional equipment on the unit access doors 2 6 1...

Page 17: ...g and raising the fans Hold the fan assembly down so the top plate is on the floor of the cabinet as shown in Figure 12 Align the two holes in each corner of the top plates with the threaded inserts i...

Page 18: ...mount the sensor Temperature Humidity Sensor 1 Remove the cover from the base of the sensor by squeezing it at the top and bottom CAUTION Take care not to damage the exposed tem perature humidity sens...

Page 19: ...sor may be used for supply air control The sensor is field installed in the supply air stream The supply air temperature and humidity are monitored by the system controller and compared to limit value...

Page 20: ...densate drain line 2 7 Piping Connections 2 7 1 Chilled Water Hot Water Pipe connections for the chilled water and optional hot water reheat piping are sweat connections In most cases they terminate i...

Page 21: ...NOTE 2 Figure 16 Condensate Pump If an optional field installed condensate pump is used a p trap must be installed to allow proper condensate drainage see Figure 16 The height of the trap must be a m...

Page 22: ...required WARNING Verify power is turned off before making connections to the equipment NOTE All wiring must conform to local and national electrical code requirements Use of copper conductors only is...

Page 23: ...g 6 Power Switches Motor Starter Protectors Quantity Varies 7 Water Detector Control Module Optional CAUTION Prior to unit operation an adequate unit to earth ground must be connected to the unit 2 8...

Page 24: ...electrical box see Figure 18 If customer furnished the wire insulation must be rated at 600V Refer to the electrical schematic supplied with your unit for proper wire terminations 2 9 System Settings...

Page 25: ...e humidifier Visually check for vapor leaving the steam head or feel if the cylinder is warm to verify if the humidifier is operational In all cases 1 to 6 hours might be required to see a desired lev...

Page 26: ...as automatic controls may start them unexpectedly 4 1 1 Compact CWE Precision A C Unit 4 1 1 1 Air Filter The air filter is usually the most neglected item in an air conditioning system To maintain e...

Page 27: ...10 VDC control signal to the fan s Refer to the electric drawing to determine the correct I O board terminal numbers This must done within 15 seconds of turning the disconnect switch On or the control...

Page 28: ...ped see item immediately above e Heater element burned out Check continuity with an ohmmeter Replace heater element Hot Water Heater a Low hot water flow Check hot water flow at supply source Inoperab...

Page 29: ...s When repairs are completed remove all traces of flux After any repair pressurize the system to check for leaks prior to recharging the system 4 4 4 3 1 3 Humidifier Cylinder Replacement After an ext...

Page 30: ...Push the On Off Drain switch to the On position 17 Replace the cover on the electric box and turn the main power disconnect switch to the On position 18 Turn on the water supply to the humidifier 19 T...

Page 31: ...han UPS ground the customer is responsible for the shipping charges If you do not have established credit with SATS you must give a freight carrier account number A written or faxed purchase order is...

Page 32: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 33: ...y line connected to humidifier If required If shut off valve is installed open valve 9 Safety pan installed under ceiling mounted equipment if required 10 Filter s installed if required 11 Ductwork co...

Page 34: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 35: ...perate Properly Semi Annually Tighten Electrical Connections Clean Unit as Necessary Check Contacts on Contactors Clean Coils for Pitting Clean Condensate Pump Heat Reheat Operational Annually Inspect...

Page 36: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 37: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc NOTES...

Page 38: ...Mar 2012 Compact CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc...

Page 39: ...Load Amps FOB Freight on Board HACR Heating Air Conditioning Refrigeration HP Horse Power Hz Hertz IAQ Indoor Air Quality in w g Inches of Water Gauge kVA Kilo Volt Amps kW Kilowatt MAX CKT BKR Maxim...

Page 40: ...t CWE Series Installation Operation Maintenance Manual Air Technology Systems Inc OZZ0003 Rev E March 2012 Compact CWE Series Installation Operation and Maintenance Specifications are subject to chang...

Reviews: