AIR BOOSTER 2
EN/10.2018/IT30I © STULZ SpA – all rights reserved
Motor
blocked
,
Alarm conditions occur when:
- Ctr
= PrS (pressure
control)
- i2F
= Mtr
Alarm is signalled if Dig-in 2
(DI2) is active for a time ≥
Normal operating condition is restored
when:
-
Dig-in is deactivated
-
Press the DOWN key for 3 sec
The alarm is also disabled by:
a. Instrument restart shutdown
b. Cycle of Stand-by/Off followed by restart.
Manual
“Mtr” message appears on
the display alternated with
standard display.
Motor blocked alarm will
open K1 relay and bring
An-out AO1 and AO2 to 0 V.
Faulty “Upper
Temperature”
probe B1
There will be the probe alarm
if configured: b1 = y.
Alarm is signalled after
approx 10 seconds.
Automatic
Fault probe alarm will bring
An-out AO1 and AO2 to 0
= tPr (temp control)
= b1 or Avr or MAu.
Faulty
“Middle
Temperature”
probe B2
There will be the probe alarm
if configured: b2 = y.
Alarm is signalled after
approx 10 seconds.
Automatic
Fault probe alarm will bring
An-out AO1 and AO2 to 0
= tPr (temp control)
= b2 or Avr or MAu.
Faulty “Lower
Temperature”
probe B3
There will be the probe alarm
if configured: b3 = y.
Alarm is signalled after
approx 10 seconds.
Automatic
Fault probe alarm will bring
An-out AO1 and AO2 to 0
= tPr (temp control)
= b3 or Avr or MAu.
Faulty
pressure
probe
There will be the probe alarm
if configured: b4 = y.
Alarm is signalled after
approx 10 seconds.
Automatic
Fault probe alarm will bring
An-out bring AO1 and
AO2 to 0 V if
= PrS
(pressure control)
Find below the table with the list of alarm messages:
Label
Meaning
Mode
b1
Probe B1 alarm
Flashing
b2
Probe B2 alarm
Alternated with temperature
b3
Probe B3 alarm
Alternated with temperature
b4
Probe B4 alarm
Alternated with temperature
HA
High temperature alarm
Alternated with temperature
LA
Low temperature alarm
Alternated with temperature
HP
High pressure alarm, manual reset
Alternated with temperature
Fan
Automatically reset “Fan Blocked” alarm
Alternated with temperature
Fnb
Manually reset “Fan Blocked” alarm
Alternated with temperature
dMP
Manually reset “Damper Blocked”
Alternated with temperature
Mtr
Manually reset “Motor Blocked” alarm
Alternated with temperature
OFF
Off state from key display
Only message
Stb
Stand-by state from digital input 1 display
Only message
noL
No communication between keypad and base
Only message
nu
Trying to view a probe that is declared missing
Only message
The activation of any alarm involves:
• The activation of the buzzer and the activation of the alarm output;
• The display of the relative notification alarm (in flashing mode), on a rotating basis together with
existing alarms alternated with displayed probe by default (
). If the display also shows faulty
probe alarm, the display will show the alarms on a rotating basis.