To unlock the keypad: hold down UP and DOWN keys for few seconds, until “POn” starts to flash.
Manual reset after locking alarms
If the unit is locked, press DOWN key for 3 seconds to reset the unit. It allows MANUAL UNLOCK
function (manual reset of alarms) when the unit is locked due to:
• FAN BLOCKED alarm (at least 4 events in 4 hours)
• DAMPER BLOCKED alarm
• MOTOR BLOCKED alarm
• HIGH PRESSURE alarm
5.2. Parameters
Label Description
Range
Preset
value
SPt
Temperature setpoint (Type 1)
]
25°C
SPb
Pressure setpoint (Type 2)
÷
]
20 Pa
LS
Temperature setpoint lower limit
5°C
US
Temperature setpoint upper limit
°C [
÷ 230]
50°C
LSb
Pressure setpoint lower limit
Bar [0 ÷
] PA [0 ÷
]
10 Pa
USb
Pressure setpoint upper limit
Bar [
÷ 50,0] PA [
÷ 725]
80 Pa
Ctr
Type of control tPr÷ PrS
tPr (temperature control) ÷ PrS (pressure control)
tPr
CMt
Temperature control mode
BAF (Air Booster Fan) ÷ BAM (Air Booster Modulator)
BAF
CF
Temperature unit of measurement: Celsius, Fahrenheit
°C(0) - °F(1)
°C
rES
Resolution (only for T in °C): decimal , integer
dE(0) - in(1)
dE
PMU
Unit of measurement of the Pressure
Bar(0) - PA(1)
PA
Lod
Display probe selection by default
b1 = probe P1 (upper temp)
b2 = probe P2 (middle temp) / b3 = probe P3 (lower temp)
Avr = average temperature of the enabled probes
MAu = Maximum temperature value of the enabled probes
Avr
tIP
Calculated temperature
b1 = probe P1 (upper temp)
b2 = probe P2 (middle temp) / b3 = probe P3 (lower temp)
Avr = average temperature of the enabled probes
MAu = Maximum temperature value of the enabled probes
Avr
HY
Temperature proportional band
°C [0,1÷ 25,5] °F [1 ÷ 45]
10°C
Int
Integral time for the temperature adjustment
0 ÷ 999 (seconds)
0 sec
HL
Temperature switch-off hysteresis
°C [0,1÷ 25,5]
3°C
HP
Pressure switch-off hysteresis
Bar [0,1÷1,0] Pa [1 ÷ 10]
30 Pa
LAF
Minimum speed with
= BAF
20%
UAF
Maximum speed with
= BAF
÷ 100
100%
LAM
Lower operating limit with
= BAM
10%
UAM
Upper operating limit with
= BAM
100%
bPb
Pressure proportional band
Bar [0,1 ÷ 25,5] PA [1 ÷ 360]
20 Pa
Inb
Pressure integral time
0 ÷ 999 (seconds)
0 sec
Lab
Lower operating limit with
= PrS
10%
UAb
Upper operating limit with
= PrS
÷100
100%
ton
Delay upon start-up
0 to 255 seconds
0 sec
toF
Delay upon shutdown
0 to 255 seconds
0 sec
ALL
Low temperature alarm
] °F [-40 ÷
]
5°C
ALU
High temperature alarm
÷ 110,0] °F [
÷ 230]
50°C
HLA
Low temperature alarm hysteresis
(differential for low temp alarm to be restored)
°C [0.1 ÷ 25,5] °F [1 ÷ 45]
2°C
HHA
High temperature alarm hysteresis
(differential for high temp alarm to be restored)
°C [0.1 ÷ 25,5] °F [1 ÷ 45]
2°C
ALd
Temperature alarm delay (in normal mode)
0 to 255 seconds
20 sec
dAo
Temperature alarm exclusion at power on
0 to 255 seconds
60 sec