ALP
High pressure alarm
0,1 ÷ 50 Bar; 0 ÷ 725 PA
300 Pa
HPA
High pressure alarm hysteresis
(differential for high pressure alarm to be restored)
0,1 ÷ 25,5 Bar; 1 ÷ 360 PA
10 Pa
dAP
Pressure alarm delay (in normal mode)
0 to 255 seconds
20 sec
b1
Presence of Probe P1 (Upper temperature)
n (no) - y (yes)
yes
OF1
Calibration probe (ntc) P1
°C [-12,0 ÷ 12,0] °F [-21 ÷ 21]
0°C
b2
Presence of probe P2 (Middle temperature)
n (no) - y (yes)
yes
OF2
Calibration probe (ntc) P2
°C [-12,0 ÷ 12,0] °F [-21 ÷ 21]
0°C
b3
Presence of probe (ntc) P3 (Lower temperature)
n (no) - y (yes)
yes
OF3
Probe P3 calibration
°C [-12,0 ÷ 12,0] °F [-21 ÷ 21]
0°C
b4
Presence of probe (mA) P4 (Air Pressure)
n (no) - y (yes)
no
OF4
Calibration probe P4
Bar [-12,0 ÷ 12,0] PA [-21 ÷ 21]
0 Pa
LCi
Pressure probe scale start
[-1,0 Bar] [-15 PA] ÷
0 Pa
UCi
Pressure probe scale end
÷ [50 Bar] [725 PA]
250 Pa
i1F
Digital input 1 function
nu(0) - OFF(1) where ‘nu’= not used
nu
i1P
Digital input 1 polarity
OP(0) - CL(1)
CL
i2F
Digital input 2 function
nu = Disabled
Fan = Fan Blocked Alarm (
Ctr
= tPr/
= BAF)
dMP = Damper Blocked Alarm (
Ctr
= tPr/
= BAM)
Mtr = Motor Blocked Alarm (
Ctr
= PrS)
Fan
i2P
Digital input 2 polarity
OP(0) - CL(1)
OP
t2d
Digital input 2 alarm delay
0 to 255 seconds
10 sec
AdP
Analogue output percentage for damper alarm
20%
OPC
ON-OFF key enabling
no(0) - yes(1)
yes
AOP
Alarm output polarity
OP(0) - CL(1)
OP
tbA
Silencing the Alarm
no(0) - yes(1)
no
Adr
Serial Address
1 ÷ 247
1
br
Baud Rate selection
96(0) - 192(1)
9600
rEL
Firmware release code
read only
Ptb
EEPROM map identification
read only
INFORMATION
Marked parameters of the list above are not used on BAF units.
5.3. Setting the operating mode
The controller can use 2 different types of input, mutually exclusive and that are selected with
parameter
, Control type.
= tPr: Temperature control, with up to 3 temperature probes, NTC 10K type at 25°C;
= PrS: Pressure control, with an input of 4-20mA type, connected to the pressure transducer.
INFORMATION
When the control type is selected, only the sensors assigned to it are taken into account. For
example, a connected pressure probe is not considered in the temperature control mode.
The probe value is displayed only if the probe is connected. If the probe is not used and not
connected, “nu” (not used) label appears on the display.