AIR BOOSTER 2
EN/10.2018/IT30I © STULZ SpA – all rights reserved
5.3.1. Temperature control
The parameters involved for temperature control are:
,
After the selection of temperature control, select the type of application via parameter
.
= BAF: Air Booster Fan -> Fan Mode
Fan Mode
The parameters involved for fan mode of temperature control are:
,
,
,
.
• The control must command an electronic fan.
• The associated digital output will be K1 and it will be enabled when the controller is set to ON,
after the delay upon start-up (
• The associated analogue output will be equivalent on both outputs AO1 and AO2 and will be
enabled after the delay upon start-up (
• The control signal depends on the setting of temperature calculation parameter (
).
Proportional adjustment
SWITCH-ON:
• The analogue output will be 0 if:
-
• The analogue output will be at the minimum speed value (
) with:
-
• The analogue output will be at the maximum speed value (
+
• The intermediate values will be calculated based on the two extreme values reported above
SWITCH-OFF:
• The analogue output will be 0 if:
-
• The analogue output will be at the minimum speed value (
) with:
-
• The analogue output will be at the maximum speed value (
INFORMATION
If
=0 (temperature switch-off hysteresis equal to zero), activation and deactivation on
temperature setpoint (
) occurs; the minimum value for the required operation to be
attributed to parameter
Adjustment PI
The analogue output will modulate between minimum (
) speed value, in order
to reset the error between temperature calculation (
) and temperature setpoint (
), considering
the temperature proportional band (
) as a proportional component and integral time for temperature
adjustment (
) for the calculation of the integral part. With an integral type of adjustment, the steady-
state system can always reach the setpoint if the load conditions are constant.
5.4. System states
The parameters involved are:
,
Switch-on adjustment delay
Upon switch-on, in “System ON” state, the controller will wait for the delay upon start-up time (
before starting to regulate. This not only applies to the switch-on, but also when switching from
“System OFF” to “System Stand By” or to “System ON”.