Contact Power Pack Sensor System
42
Contact Power Pack Non-Dim Switch Module
Note: All dimensions shown in inches.
AC Input Voltage:
Dual Voltage Input (120V ~ 277 VAC, 60 Hz)
• 120 VAC, 60 Hz (108 to 132 VAC)
• 277 VAC, 60 Hz (262 to 292 VAC)
Loads:
Model
Volts
Tungsten
Ballast
61330
120
15A (1800VA)
20A (2400VA)
277
Not Applicable
8.66A (2400VA)
61331
120
15A (1800VA)
20A (2400VA)
277
Not Applicable
8.66A (2400VA)
61332
120
15A (1800VA)
15A (1800VA)
277
Not Applicable
6A (1800VA)
DC Output Voltage:
+12 VDC, Unregulated
DC Output Current:
150 mA (max.)
Operating Temp:
0 - 50 degrees Centigrade, 32 - 122 degrees Fahrenheit
Dimensions:
4 inches (H) x 4 inches (W) x 2.25 inches (D) - 61330 / 61331
4-11/16 inches (H) x 4-11/16 inches (W) x 2.25 inches (D) - 61332
Compliance:
UL and cUL Listed
2 1/4"
SIDE VIEW
TOP VIEW
X
X = 4" (61330 / 61331)
4-11/16" (61332)