Manual Configuration of a Ceiling Occupancy Sensor
Note:
The preferred method of configuring Contact ceiling mounted sensors is safely from
the floor using the 61337 Contact Infrared Remote Sensor Programmer (see page 16).
However, if the Infrared Remote Sensor Programmer is lost, and the sensor units can be
reached in a safe manner, they may be programmed via the "Manual Configuration" method as
follows.
There are two programming switches (buttons) on the Ceiling Occupancy Sensor which can be
used to Display and Modify the Sensor’s Settings. Programming Switch 2, the "Field" Button
(turns on the Blue LED when pressed) is used to select the Field you wish to display or mod-
ify. Programming Switch 1, the "Setting" Button (turns on the Green LED when pressed) is
used to set the value of the selected Field. By using both buttons, the Sensor can be manually
configured for most applications.
Note:
Use the Contact IR Remote Sensor Programmer for faster programming of all features.
Refer to "Using the Programming Remote" on page 16.
To enter Manual Programming Mode:
Step 1. Unscrew Lens Cover on Ceiling Sensor
to access manual programming buttons.
Step 2. Press and hold the Field Button for 3
seconds. After 3 seconds the Red LED
will turn on indicating the unit is in the
Manual Programming Mode. Release the
button.
To exit Manual Programming Mode:
There are three ways to exit the Programming
Mode.
Step 1. Press and hold the Field Button for 3
seconds.
Step 2. Keep tapping the Field Button until
Ceiling Sensor exits Programming Mode.
Step 3. Stop tapping the buttons. The Ceiling Sensor will exit the Programming Mode 1
minute after the last button press.
Note:
Test Mode may be entered by holding the SETTINGS button for 10 seconds. The
sensor will automatically exit the Test Mode after 4 minutes. (Sensor
must not
be in the
Programming Mode.)
Programming
Switch 1 (Setting)
GREEN
Programming
Switch 2 (Field)
BLUE
Figure 3: Manual Programming