Exposure Points
H-6
StorageTek SL8500 User's Guide
■
It must have a high flexibility and low porosity to effectively cover the irregular
textures of the subject area, and to minimize moisture migration and water
damage.
■
The encapsulant must not out-gas any harmful contaminants. Many encapsulants
commonly used in industry are highly ammoniated or contain other chemicals
that can be harmful to hardware. It is very unlikely that this out-gassing could
cause immediate, catastrophic failure, but these chemicals will often contribute to
corrosion of contacts, heads or other components.
Effectively encapsulating a subfloor deck in an on-line computer room is a very
sensitive and difficult task, but it can be conducted safely if appropriate procedures
and materials are used. Avoid using the ceiling void as an open supply or return for
the building air system. This area is typically very dirty and difficult to clean. Often
the structural surfaces are coated with fibrous fire-proofing, and the ceiling tiles and
insulation are also subject to shedding. Even before filtration, this is an unnecessary
exposure that can adversely affect environmental conditions in the room. It is also
important that the ceiling void does not become pressurized, as this will force dirty air
into the computer room. Columns or cable chases with penetrations in both the
subfloor and ceiling void can lead to ceiling void pressurization.
Exposure Points
All potential exposure points in the data center should be addressed to minimize
potential influences from outside the controlled zone. Positive pressurization of the
computer rooms will help limit contaminant infiltration, but it is also important to
minimize any breaches in the room perimeter. To ensure the environment is
maintained correctly, the following should be considered:
■
All doors should fit snugly in their frames.
■
Gaskets and sweeps can be used to address any gaps.
■
Automatic doors should be avoided in areas where they can be accidentally
triggered. An alternate means of control would be to remotely locate a door trigger
so that personnel pushing carts can open the doors easily. In highly sensitive areas,
or where the data center is exposed to undesirable conditions, it may be advisable
to design and install personnel traps. Double sets of doors with a buffer between
can help limit direct exposure to outside conditions.
■
Seal all penetrations between the data center and adjacent areas.
■
Avoid sharing a computer room ceiling or subfloor plenum with loosely controlled
adjacent areas.
Filtration
Filtration is an effective means of addressing airborne particulate in a controlled
environment. It is important that all air handlers serving the data center are
adequately filtered to ensure appropriate conditions are maintained within the room.
In-room process cooling is the recommended method of controlling the room
environment. The in-room process coolers re-circulate room air. Air from the hardware
areas is passed through the units where it is filtered and cooled, and then introduced
into the subfloor plenum. The plenum is pressurized, and the conditioned air is forced
into the room, through perforated tiles, which then travels back to the air conditioner
for reconditioning. The airflow patterns and design associated with a typical computer
room air handler have a much higher rate of air change than typical comfort cooling
air conditioners so air is filtered much more often than in an office environment.
Summary of Contents for SL8500
Page 1: ...1 StorageTek SL8500 User s Guide E20869 12 March 2017...
Page 12: ...xii...
Page 16: ...Installing Web launched SLC 1 4 StorageTek SL8500 User s Guide...
Page 32: ...Maximizing Library Performance when Partitioning 5 6 StorageTek SL8500 User s Guide...
Page 38: ...Guidelines for using CAPs 6 6 StorageTek SL8500 User s Guide...
Page 46: ...Maximizing Library Performance Though Cartridge Placement 8 6 StorageTek SL8500 User s Guide...
Page 62: ...Monitoring Library Events 12 6 StorageTek SL8500 User s Guide...
Page 66: ...Rebooting a Robot 13 4 StorageTek SL8500 User s Guide...
Page 80: ...A 2 StorageTek SL8500 User s Guide...
Page 94: ...whereAmi B 14 StorageTek SL8500 User s Guide...
Page 108: ...Firmware Upgrades with RE D 4 StorageTek SL8500 User s Guide...
Page 138: ...World Wide Name Glossary 10...