Connection
ID 441758.05
16
Commissioning Instructions I/O Terminal Module
4
WE KEEP THINGS MOVING
TTL/HTL switchover REA 5001
The identification of the switches and the assignment of the switch positions to the function (HTL/TTL) are
shown on the PCB cover of the REA 5001.
Terminal description X102 – XEA 5001
NOTICE
Machine movement due to unexpected target value
If the analog input is not switched, the inverter will detect a target value default of +5 V.
Always operate the inverter with a switched analog input.
2 leads with the same cross-section
with double cable end
—
Switch
TTL/HTL Conversion
S0
BE3
S1
BE4
S2
BE5
maximum conductor cross-section
Connection type
maximum conductor cross-section
[mm
2
]
REA 5001
S0
S1
S2