Connection
Commissioning Instructions I/O Terminal Module
13
ID 441758.05
WE KEEP THINGS MOVING
4
4
Connection
4.1
X100-X103: Analog and Binary Signals
WARNING!
Danger of machine malfunction due to EMC interference!
Do not use cables longer than 30 m (leads to binary inputs, binary outputs, analog inputs and analog
outputs)!
Terminal description – X100 – SEA 5001, REA 5000, REA 5001, XEA 5001
NOTICE
Machine movement due to unexpected target value
If the analog input is not switched, the inverter will detect a target value default of +5 V.
Always operate the inverter with a switched analog input.
Information
Remember that the scanning time and update rate T
A min
depend
on the complexity of the user program on the inverter. Both times
can assume the values 1, 2, 4, 8, 16 or 32 ms depending on the
scope of the user program. Also consider the setting of parameter
A150 cycle time
.