Use weight (charging) scale:
A scale (P/N 2010-0000) must be used to
indicate when the recovery tank is 80% full when the STINGER does not
have the 80% Shutoff Kit option installed.
x
Avoid dangerous environments:
Although the unit can be used
outdoors, we do not recommend operation in the rain, or in wet locations.
Secure the unit when working above floor level. This equipment should
not be used in the vicinity of spilled or open containers of flammable
materials.
x
Ventilation requirements:
This equipment should be used in a location
with mechanical ventilation that provides at least 4 air changes per hour,
or the equipment should be located at least 18" above the floor.
x
Use recommended accessories:
Follow the instructions that
accompany all accessories. Improper use of accessories may damage
the equipment or create a hazard.
x
Repair damaged parts:
Do not operate the unit with a defective part.
Repair unit to proper operating conditions.
Specifications
Refrigerant Recovery Rates - Certified per AHRI 740-95 & 740-98
Refriger-
ant
Liquid
Rate
Liquid Rate
(Push-Pull)
Vapor Rate
Vacuum Level
(inches Hg)
R-22
3.53 lb/min
1.60 kg/min
12.30 lb/min
5.58 kg/min
0.29 lb/min
0.13 kg/min
>15
R-134A
2.67 lb/min
1.21 kg/min
10.98 lb/min
4.98 kg/min
0.22 lb/min
0.10 kg/min
>15
R-410A
3.02 lb/min
1.37 kg/min
14.62 lb/min
6.63 kg/min
0.22 lb/min
0.10 kg/min
>15
Summary of Contents for Refrigerant Recovery Unit
Page 9: ...2090 0217 Rev 6 9 Descriptions of Features Figure 1 Stinger Front View...
Page 15: ...2090 0217 Rev 6 15 Figure 3 Standard Recovery Hose Connections...
Page 18: ...18 2090 0217 Rev 6 Figure 4 Liquid Push Pull Recovery Operation...
Page 21: ...2090 0217 Rev 6 21 Figure 6 Special Notes for R410 A Recovery...
Page 26: ...26 2090 0217 Rev 6 Figure 8 Recovery Tips...
Page 30: ...30 2090 0217 Rev 6 Schematic Diagram Figure 9 Schematic Diagram...
Page 32: ...32 2090 0217 Rev 6 Figure 10 Stinger Exploded View...
Page 34: ...34 2090 0217 Rev 6 Figure 11 Compressor Exploded View...