COmmISSIONING
Controller menu
www.stiebel-eltron.com
STE |
43
EN
GL
ISH
Alarm limit deviation
f
f
Set a temperature at which an error message is displayed on
the appliance.
Alarm delay
f
f
Set a time after which an error message is displayed on the
appliance.
Cascade control
Cascade control
Slave = 0, Master = 1
WPE-I H Premium heat pumps
Number of secondary WPE-I H Premium
Ext. controllable heat pumps
Heat pump ID
Port number
Parameter
Number of ext. controllable heat pumps
Number of heat pumps of a different series
Communication mode
Broadcast address
In this menu, specify which heat pumps are the primary heat pump
and the secondary heat pumps. The primary heat pump controls
the complete cascade. Some settings can be made on the second-
ary heat pumps. If there is communication between the primary
and secondary heat pumps, the heat pump ID is displayed on the
secondary heat pump screen.
f
f
If you make changes in this menu, all the heat pumps must
be restarted.
f
f
If the primary heat pump is not communicating with the
secondary heat pump, reinitialise the secondary heat pump.
Restart the secondary heat pump. Observe the chapter “Com-
missioning / Commissioning cascades”.
Possible causes for faulty communication can be found in chapter
“Commissioning / Commissioning cascades / Messages”.
Cascade control
f
f
Activate or deactivate the function.
When the function is activated, multiple heat pumps can be in-
stalled in the heating system.
Slave = 0, Master = 1
Can only be adjusted if the “Cascade control” function is activated.
f
f
Input whether the heat pump is being set up as a primary
(master) or secondary (slave) heat pump.
WPE-I H Premium heat pumps
Note
Use this menu item if further heat pumps of the same
series are installed in your heating system.
Can only be activated if the “Cascade control” function is switched
on and the heat pump is set up as a primary heat pump.
f
f
Activate or deactivate the function.
When this function is activated, further heat pumps of the same
series can be set up.
Number of secondary WPE-I H Premium
Can only be activated if the “WPE-I H Premium heat pumps” func-
tion is switched on.
f
f
Set the number of secondary heat pumps that can be con-
trolled by the primary heat pump.
Ext. controllable heat pumps
Note
Use this menu item if heat pumps of a different series are
installed in your heating system.
Can only be activated if the “Cascade control” function is switched
on and the heat pump is set up as a primary heat pump.
f
f
Activate or deactivate the function.
When this function is activated, heat pumps of a different series
can be connected to the primary heat pump.
f
f
In the menu, change to the last page.
f
f
Tap on the button to add a heat pump of a different series.
Ext. heat pumps
f
f
Assign a heat pump ID ≥ 1 to the secondary heat pump. As-
sign IDs in chronological order for further secondary heat
pumps.
EM3
kW
f
f
Set the secondary heat pump output.
Heat pump ID
Can only be entered if the “Cascade control” function is switched
on and the heat pump is set up as a secondary heat pump.
f
f
Assign a heat pump ID ≥ 1 to the secondary heat pump. As-
sign IDs in chronological order for further secondary heat
pumps.
Port number