75
08/13424999756
Start up procedure and trial run
Completion work
Insert the glass panes in all SHE manual call points. Close the control panel door.
Stick on the service contact telephone number.
Attention:
If the trial run fails, repeat the initial start up procedure!
Troubleshooting
Display - operating OK - is not shining
in the SHE manual call points and the control panel:
•
a malfunction has occurred (see malfunction beep code chart, page 26), eliminate the malfunction.
•
mains power connection out of order:
check mains supply lead / voltage
check mains fuse
•
batteries out of order:
check battery fuse
check battery connection
defective batteries, to be replaced
The drives open without pressing a switch
•
SHE manual call point incorrectly connected or defective, check and correct
•
automatic smoke detector soiled, replace
•
due to a fault vent switch in permanent contact
Vent switch with reversed function
•
reverse connection at the vent switch or in the control panel
Vent switch without function
•
Vent switch incorrectly connected
•
SHE activated, press Reset switch in the control panel
•
No voltage to mains supply lead, repair
•
Mains fuse defective, replace
•
Motor fuse defective, replace
•
Wind/rain alarm pending (additional module only)
Capacitance of storage batteries is inadequate for 72 h network compensational operation
The measurement of the current draw for testing the capacitance of the storage batteries has to be done in standby
mode. It may not happen directly after a motor activation. The standby mode starts automatically after approx. 3 min
when SHE-Reset is activated or after the last ventilation operation.
All LED displays are dark (without mains 230 V/50 Hz)
•
Discharge totally battery, take off battery fuse disconnect emergency batteries and wait at least 2 min.
•
Replace by new emergency batteries and connect them, replace battery fuse
The green LED
OK
is dark
•
Mains connection out of order
•
Mains fuse defective
•
Battery out of order
•
Battery fuse defective
Adhesive magnet falls after a moment in spite of time “Closed”
•
DIP-Switch 3 is not set to ON. Function of the control panel to secure the door
Compact control panel 4A, 4A/M und 8A, 8A/M