64
08/13424999756
Compact control panel 4A, 4A/M und 8A, 8A/M
Description of operating
Manual activation in case of fire/smoke/alarm
Smoke heat extraction / opening windows
Press the red OPEN switch
at a SHE manual call point, the windows open completely, the red LED display -
-
SHE activated - is shining at all SHE manual call points, the ventilation function is out of order.
Smoke heat extraction / closing windows
Press the switch “closed”
at a SHE manual call point, the windows are closing, the red LED display
SHE
activated - goes out at all SHE manual call points, the ventilation function is working again.
Note:
there is no reset of the connected and activated automatic detectors!
Automatic activation in case of fire/smoke/alarm
(if automatic detectors are connected only)
Smoke heat extraction / opening windows:
Smoke heat extraction / opening windows Smoke reaches the automatic detectors, the windows are opened completely,
the red display in the automatic detector is shining, the red LED display
SHE activated - is shining at all SHE manual
call points, the ventilation function is out of order.
Smoke heat extraction / closing windows
Press the switch “closed”
at a SHE manual call point, the windows are closing, the red LED display
SHE
activated - goes out at all SHE manual call points, the yellow LED display
- malfunction - flashes.
Note:
there is no reset of the connected and activated automatic detectors!
Reset of automatic detectors
Set the automatic detectors free from smoke by blowing out or replace them in case of heavy soiling. Press the RESET
switch on the basic circuit control board of the control panel, the windows are closing, the red display in the automatic
detectors goes out, the red LED display
SHE activated - goes out at all SHE manual call points, the yellow LED
display
malfunction - goes out, the ventilation function is working again.
Daily ventilation
(if vent switches are connected only)
Opening windows
Press the switch “open” at the vent switch, the windows open completely. (Interruption of the opening by pressing both
switches together (Open and Closed) = STOP or by Stop switch depending on vent switch).
Closing windows
Press the switch “closed” at the vent switch, the windows close completlely. (Interruption of the opening by pressing both
switches together (Open and Closed) = STOP or by Stop switch depending on vent switch). In case of mains or battery
failure, the windows close immediately.
Automatic ventilation control
If activated (see putting into operation), the windows are closing automatically after xx min. (10 min. factory-made), in
case of mains or battery failure, the windows close immediately. See also page 69, DIP-Switch 12.