SSDK12M - SSDK16M - SSDK20M
23
● Check plug with a brown & blue wires is not loose.
● Oil change and oil filter replaced highly recommended.
● Check the radiator fins are not obstructed/dirty.
● Check the radiator is not damaged or leaking coolant.
Main AC Alternator
High AC Voltage
Low AC Voltage
Shutdown
Fail To Stop
Shutdown
Fan Belt
Fault Icon
Possible Cause
Check
High Hz/Frequency could indicate the engine is running too fast.
● Using the fuel pump prime button, prime the fuel system
to expel any trapped air within.
Fuel System
If none of the above solve the issue then a closer inspection of the engine would be advised e.g.
check that no-one has adjusted the engine speed - consult an engine specialist.
Shutdown
Coolant Level
●
Check the temperature switch operation - Ref. wiring
diagram - replace if necessary.
DO NOT USE THE
GENERATOR WITHOUT A TEMPERATURE SWITCH FITTED.
Temperature Switch
● Check wiring from the oil pressure switch to the DSE 3110
- Ref. wiring diagram.
Service
A
High Engine Temperature
shutdown could be for two main reasons, either the
engine has overheated or the temperature switch or wiring is faulty.
If the temperature gauge shows a high temperature (> 100
⁰C) and the generator is shutting
down with all the above checked, then the issue could be an engine component e.g.
thermostat, water pump etc. - consult an engine specialist.
High Hz/Frequency
The DSE 3110 is displaying the correct no-load frequency but the generator shuts down
with the
Low AC Voltage
icon displayed.
●
Check for continuity and wiring on the AC 2A reset button
(brown wire from DSE 3110) - Replace if necessary.
2A Reset Button
● Check main alternator output - AC alternator tests would
be advisable.
Automatic Voltage Regulator -
AVR
● Check all wiring and circuits associated with the AVR.
● Start and run the generator and measure the AC voltage
across the brown & blue wires - this should measure
approximately 115V or 230V AC.
DSE 3110 Control Module
High Engine
Temperature
Canopy Obstructions
●
Check the generator canopy has no obstructions over any
vented areas - Also see
Operating Environment
in this
handbook.
Fault occurs after the
engine has fired
● Check associated wiring from the temperature switch to
the DSE 3110 - Ref. wiring diagram.
Faulty Wiring
● Check the level of the water and antifreeze level - fill with
a 50/50 mix as indicated by the sticker next to the
inspection flap.
CAUTION HOT STEAM CAN BURN!
Radiator
● Check the condition and tension of the fan belt - tighten
or replace if necessary.
The DSE 3110 is displaying the correct no-load frequency but the generator shuts down
with the
High AC Voltage
shutdown icon displayed.
● Check main alternator output - AC alternator tests would
be advisable.
Automatic Voltage Regulator
AVR
● Check all wiring and circuits associated with the AVR.
A
Fail To Stop
fault is mostly caused by the oil pressure switch not operating correctly -
See the
Service & Maintenance
section in this handbook for a detailed solution.
●
Check the oil pressure switch operation - Switch normally
closed when engine is at rest and open when engine
running - Remove, clean or replace if necessary.
Oil Pressure Switch
Main AC Alternator
Faulty Wiring