SSDK12M - SSDK16M - SSDK20M
17
Fig.13
Fig.12
400V - M6 threaded stud - Maximum tightening torque to 6.8Nm.
230V - M8 threaded stud - Maximum tightening torque to 16.5Nm
Use the black plate to mount cable gland(s) to secure the trailing cable into position.
Warning
The plate MUST be fitted when running the generator - Risk of Electric Shock.
For storage or long periods of inactivity, Stephill Generators recommend the following:
Before the generator is used after long term storage, all fuels and oils should be replaced.
The battery isolator switch should be switched off.
Generator mounts, pipes and hoses should be checked to ensure that they are un-perished following
extended periods of storage.
The generator should be stored in a clean dry area, ideally having a reasonable constant ambient
temperature, and ideally not below freezing.
Hard Wire Terminals - Connection & Location
Below the main control panel is a "HARD WIRE" facility. Once the black plate has been removed you will see
both the 230V single phase and 400V three phase terminal connections - Fig.12. Yellow labels under the
terminal connections indicate the connections - Fig.13.
When connecting to the hard wire terminals ensure the cable and crimps are the correct size. If unsure seek
advice from a qualified electrician.
Generators should be stored with oil filled to the correct capacity; Storage periods of 18 months and over
may require special lubricants and treatments. If so please seek further advice from the engine
manufacturer.
Long Term Storage