S10P Series www.stenner.com
LEVEL INPUT
The pump receives a dry contact or open collector signal from a fluid level device to
indicate a low level in the solution tank. When a signal is received on the level inputs, the
pump will stop running and the display will flash LEVEL.
If the pump stops receiving the signal, the pump continues to run and the level flashing
indicator automatically clears.
Fluid Level Device
Pump
Input
Dry Contact Relay Output
Fluid Level Device
Pump
Input
Open Collector Output
For connection to a Dry Contact
• There is no polarity to observe.
• Connect relay to Level (−), position 7 and Level (+), position 8.
For connection to an Open Collector
• Polarity must be observed.
• Connect OC positive to Level (+), position 8.
• Connect OC common to Level (−), position 7.