16400-7820 GIDOD REV A
3 - SPECIFICATIONS
EXTERIOR SIDE
INTERIOR SIDE
EXTERIOR SIDE
INTERIOR SIDE
EXTERIOR SIDE
INTERIOR SIDE
3X Outside Air Vents
OTHER CLEARANCE NOTES:
No combustible material within 6” [152] of the top and 1“ [25] of the sides of the fireplace.
No combustible material within 1” [25] around the B-Vent flue.
Steel 3” [76] surface around the fireplace opening cannot be covered with any finishing materials. Glass and decorative frame will be placed on top for both interior and exterior.
Combustible framing allowed right up to the fireplace below the viewing area only.
A combustible mantel may be placed at the top of the viewing area. Do not overlap glass.
A combustible hearth extension may be used below the viewing area on the interior side and below the outside air vents on the exterior side. Do not overlap glass.
Do not place on carpet, vinyl or soft surfaces.
6” [152] Top Standoffs; shipped flat.
Refer to Prepare The Fireplace section
for assembly instructions.
1/2” Hood Standoffs on each side.
Refer to Non-Combustible Zone section
for more information.
1/2” [13] Hood Standoffs on each side.
Refer to Non-Combustible Zone section
for more information.
CLEARANCES SHOWN ARE MINIMUM TO COMBUSTIBLES
NON-COMBUSTIBLE FRAMING AND FINISHING MATERIALS
ALLOWED RIGHT UP TO THE FIREPLACE.
X4 6” [152]
Top Standoffs
1/2” [13]
1”
[25]
6”
[152]
1”
[25]
1/2” [13]
6”
[152]
1”
[25]
1”
[25]
1/2” [13]
1/2” [13]
1”
[25]
1”
[25]
1/2” [13]
1/2” [13]
Figure 3F
F. CLEARANCES