82 of 86
Accuracy
≤±0.1 %
1
(accuracy includes adjustment, linearization,
burden influence, load influence and voltage supply
influence)
Residual ripple
≤±0.2 %
1
Electrical isolation
The analog outputs are electrically isolated from each
other and the interfaces.
Isolation voltage
50 V
1
All accuracy specifications in % from the measuring range end value of 20 mA or
10 V.
Measuring circuit monitoring of the analog outputs
Underrange:
- Current output 4 to 20 mA
- current output 0 to 20 mA
- Voltage output 0 to 10 V
dropping to 3.8 mA,
then jump to the configured signals
dropping to -0.1 mA,
then jump to the configured signals
dropping to -0.1 V,
then jump to the configured signals
Overrange
: - Current output (4 to 20) mA
- current output (0 to 20) mA
- Voltage output (0 to 10) V
rising to 20.5 mA
then jump to the configured signals
rising to 20.5 mA
then jump to the configured signals
rising to 10.25 V
then jump to the configured signals
Probe short circuit or probe and
wire break and alarms:
: - Current output (4 to 20) mA
- current output (0 to 20) mA
- Voltage output (0 to 10) V
positive signals: >21 mA,
negative signals: <3.6 mA
positive signals: >21 mA,
negative signals: <-0.1 mA
positive signals: >10.5 V,
negative signals: <-0.1 V
Output performance
The output performance (positive or
negative signals) can be set.
Summary of Contents for WRX900 Series
Page 1: ...1 of 86 ...
Page 13: ...13 of 86 3 5 Function overview Figure 6 Function review of the receiver ...
Page 45: ...45 of 86 8 2 1 Editing parameters ...
Page 65: ...65 of 86 Figure 6 Fly back functions ...
Page 69: ...69 of 86 11 3 Connect PC and receiver to each other 1 ...
Page 86: ...86 of 86 ...