56 of 86
ErHi (positive signals) and ErLo (negative signals) are possible.
The performance of the output signal in the event of underrange or overrange is
shown
in the following table.
Measuring circuit monitoring of the analog outputs
Underrange:
- current output (4 to 20) mA
- current output (0 to 20) mA
- voltage output (0 to 10) V
dropping to 3.8 mA,
then jump to the configured signals
dropping to -0.1 mA,
then jump to the configured signals
dropping to -0.1 V,
then jump to the configured signals
Overrange:
- current output (4 to 20) mA
- current output (0 to 20) mA
- voltage output (0 to 10) V
rising to 20.5 mA,
then jump to the configured signals
rising to 20.5 mA,
then jump to the configured signals
rising to 10.25 V,
then jump to the configured signals
Probe short-circuit or probe
and wire break and alarms:
- current output (4 to 20) mA
- current output (0 to 20) mA
- voltage output (0 to 10) V
positive signals: > 21.6 mA
negative signals: < 3.6 mA
positive signals: > 21.6 mA
negative signals: < -0.1 mA
positive signals: > 10.5 V
negative signals: < -0.1 V
Output performance
The output performance (positive or
negative signals) can be set.