INPUT VOLTAGE DIP SWITCH SETTING
CAUTION: DIP SWITCH VOLTAGE SELECTION MUST BE FINALIZED
PRIOR TO APPLYING POWER TO THE TIME CONTROL.
1. Do not apply power to the timer prior to setting correct input voltage using
the DIP switch.
2. Determine the input voltage using the DIP switch (see wiring diagrams).
3. Set the Dip switch according to the diagram below.
208~240VAC
277VAC
120VAC
ON
ON
ON
DP
DP
DP
1
1
1
2
2
2
3
3
3
4
4
4
NOTE: THE FACTORY DEFAULT SETTING FOR DIP SWITCH IS FOR
277VAC INPUT VOLTAGE.
CAUTION: DO NOT CHECK CIRCUITS BY SPARKING WIRES TO
TERMINALS, DAMAGE TO THE TIMER MAY RESULT.
If loads are connected to both NC and NO contactors, both contacts are derated
to 67% of the above values.
LED INDICATORS FUNCTION
Power LED (Red)
– light illuminates when power is applied to the timer.
Status LED (Green)
– light illuminates when power is applied to the loads.
DIP SWITCH CONFIGURATION
WARNING, FAILURE TO PROPERLY CONFIGURE THE DIP SWITCH
WILL RESULT IN DAMAGE TO THE UNIT AND VOID THE WARRANTY,
BEFORE INSTALLING AND WIRING THE TIME CONTROL, PROPER
CONFIGURATION MUST BE SELECTED, THIS IS ACCOMPLISHED AS
PER THE ABOVE DIP SWITCH DIAGRAM.