background image

 
 
 

ASTRO NOVA CITY 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
02/02.2015 

A016.17.56816 

 

ENG

 

 

ASTRONOMICAL TIME SWITCH 

 

FIG. 1 

1. 

Time scale 

2. 

Timetables 

3. 

Text line 

4. 

Sunrise symbol  

5. 

Low battery symbol 

6. 

Time / Date 

7. 

C1 relay status symbol 

8. 

Go down the menu / C1 manual 
operation 

9. 

Go up the menu / C2 manual 
operation 

10. 

Bluetooth dongle connector  

11. 

Cancel option / Go back in the menu 

12. 

Accept option / Enter the menu / Turn on 
the device without power supply 

13. 

C2 relay status symbol  

14. 

Manual operation (blinking) / Permanent 
manual (fixed) 

15. 

12 H / 24 H 

16. 

Transfer symbol 

17. 

Sunset symbol  

18. 

Days of the week 

 
INSTRUCTIONS FOR USE 

ASTRO  NOVA  CITY  is  a  digital  time  switch  of  astronomical  update  designed  for  the  control  of  any 
electrical  installation  that  requires  a  solar  reference,  particularly  of  the  sunrise  and  nightfall  time  in  a 
specific  location  every  day  of  the  year.  It  incorporates  the  possibility  of  performing  manoeuvres  at  a 
fixed  time  of  the  day,  as  well  as  switching  on  and  off  at  sunrise  and  sunset.  In  the  astronomical 
manoeuvres, it is possible to set a correction of up to ± 9 hours 59 minutes to both C1 and C2 channels. 
In  addition,  it  has  a  series  of  extra  functions  such  as:  automatic  change  to  daylight  saving  /  standard 
time, 4 holiday periods, adjustable screen brightness and programming from Smartphone / Tablet.  
Menus can be displayed in several languages and show a timetable on screen with the current day’s 
schedule. 
It has 2 independent and voltage-free switched circuits that allow programming of up to 40 manoeuvres 
between channel 1 and/or channel 2.  
 

INSTALLATION 

WARNING: Installation and mounting of electrical devices must be carried out by an authorised fitter. 

TURN OFF THE POWER SUPPLY PRIOR TO INSTALLATION. 

The device is internally protected against interference by a security circuit. However, some particularly 
strong fields may alter its functioning. Interference can be avoided if the following installation rules are 
taken into account:  
- The device must not be installed near inductive loads (engines, transformers, contactors, etc.) 
- It is advisable to plan a separate supply line (with a network filter where appropriate).  
- The inductive loads must be provided with interference suppressors (varistor, RC filter).  
If the time switch is used in combination with other devices in an installation, it should be made sure that 
the constituted unit does not generate extraneous disturbances.  

RESTORE SUPPLY ONCE THE DEVICE IS FULLY INSTALLED.  

 

MOUNTING 

Electronic  control  device  of  independent  mounting  in  distribution  cabinet,  with  symmetric  profile  of  35 
mm. in accordance with EN 60715 standard (DIN Rail). 
 

CONNECTION  

Connect power according to the diagram in 

FIG. 2. 

Phase and Neutral positions must be respected, checking the connections made. A  wrong connection 
may destroy the device.  

 
START-UP 

THE DEVICE MUST BE POWERED

 to be able to execute the installation control.  

The display will light up and the MAIN screen will appear.  
When  the  device  is  not  powered  the  display  remains  turned  off,  keeping  all  the  date  and  time 
programming, during the power-reserve period (10 years) thanks to the incorporated lithium battery. In 
the event of being installed without the battery, the device has a security power-reserve of approx. 48 
hours. 
With no power supply, press the 

MENU

 button, the display temporarily lights to allow programming. If no 

button is pressed after 5 seconds, the display will turn off again. 
These devices have four keys for their setting and programming.  
The display shows the following information: 

 

Timetable with the day’s manoeuvres (it disappears when it gets to a holiday period). A timetable for 
each channel with 24 divisions in which each segment represents 1 hour ON. 

  The display has a text line that will show the following information alternatively: 

-

  SUNRISE and SUNSET times for that day with associated symbol:  

Sun 

 = SUNRISE / Moon 

 = SUNSET 

-

  Selected city 

-

  Current date 

-

  PERMANENT operation 

-

  Active HOLIDAY period 

 

  Complete time 

  Manual manoeuvre symbol

It blinks when a manual switching is activated and if the switching 

is PERMANENT the symbol is fixed.  

  State of C1 / C2 circuits: ON 

, OFF 

  

 
SETTINGS 

ASTRO NOVA CITY switches are factory programmed with the current date and time as follows: 

 

  Time: 

GMT +1       

  Zone:  

In accordance with commercial order  

  Astronomical corrections:  

Disabled 

  Change Standard to Daylight Saving: 

Automatic 

  Change Daylight Saving to Standard: 

Automatic 

  Holidays: 

NO (4 periods disabled) 

  Programs: 

C1  to  C2  On  at  sunset  /  C1  and  C2  Off  at  sunrise 
(see 

FIG. 4

 
MANUAL OPERATION 

Activate  or  disable,  manually  reversing  the  state  of  the  circuits  temporarily  from  the  main  screen,  by 
pressing keys ▼ C1 or ▲ C2.   
The symbol will appear blinking on screen over the manipulated channel until we press ▼ C1 or ▲ C2 
again, returning to the previous state.  

 
 
PROGRAMMING 

Programming is based on menus and submenus through which we can move to program manoeuvres 
or  adjust  the  device.  The  main  menu  can  be  accessed  from  the  standby  screen  pressing  the 

 

key. 

With keys ▼ and ▲ we will move through the different menus and pressing 

 

we will access them. To 

go back to the previous menu we press the 

key.  

The details to be programmed always appear blinking on screen.  
 
 
 
 
 

3

2

1

N

L

~

6

5

4

P1 (C1 ON)
P3 (C2 ON)

on

off

600 VA

3000 W

2000 VA

1200 VA

3000 W

90 VA

400 VA

1

C

C1

C2

0

3

6

9 12 15 18 21 24

RESET

MENU

3

4

5

6

16

15

14

13

17

18

7

8

9

12

11

2

10

FIG.1

FIG.2

35

88

60

65

FIG.5

FIG.3

FIG.4

P2 (C1 OFF)
P4 (C2 OFF)

Reviews: