Ethernet CPU module and
power module for Zone 1/Class I, Div.1
Series 9441, Series 9444, Series 9492
6.1.7 Manually backing up Diagnostic Data
The diagnostic data is stored in the RAM during operation.
The diagnostic data from the RAM is backed up to Flash storage every 24 hours or in the
event of a serious error.
Backed up diagnostic data is also available after a reset or recommissioning.
If a CPU module is disconnected from the network without the diagnostic data being lost,
this data must be backed up manually.
LCD display
Settings
12309E00
Press the [Enter] key twice to switch from the system level to the
information/service level.
The following display appears (shown on the left).
12320E00
Press the ◄ or ► key until the following display appears
(shown on the left).
Only possible with active CPU module!
12327E00
Press the [Enter] key to manually back up diagnostic data.
The following display appears (shown on the left).
Press the [ESC] key to leave the sub-menu.
CPU 0-0: Status
NoDataExch
CPU 0-0:saveDiag
<
>
CPU 0-0:saveDiag
saving ...