Ethernet CPU module and
power module for Zone 1/Class I, Div.1
Series 9441, Series 9444, Series 9492
6.1.5 Displaying Information about I/O Modules
General I/O modules
LCD display
Settings
12309E00
Press the [Enter] key to switch from the system level to the
module level.
The following display appears (shown on the left).
Use the ◄ or ► keys to select the required module.
Press the [Enter] key.
The display switches to the information level/service level.
The following displays show the same design for all I/O modules.
LCD display
Display/function
12268E00
Display of the slot, module type and module status.
Possible module statuses:
Status information
on the LCD display
Meaning
Prio
IOM no response
Communication with the module is not
possible. The module is defective or not
connected, or both BusRails and/or the
BusRail connecting cable are damaged.
1
hardware failure
The module reports a hardware fault. 2
conf unequal mod
Configuration error or the wrong module
was plugged in.
3
HW disable outp.
The outputs disconnected by an
external switch (Plant-Stop)
(only with DOM 9475/2)
4
prim. Rail fail
No communication via primary BusRail
data bus
5
red. Rail fail
No communication via redundant
BusRail data bus
5
module OK/mode: x
Module is OK. No module error.
Signal errors are still possible.
The configured operating mode
(mode:x) is also displayed.
6
In case of several faults only the fault with the highest priority is
displayed. After eliminating this fault the next fault with the next
highest priority is displayed.
CPU 0-0: Status
NoDataExch
slot 2: AOM
module OK/mode:0