218129 / 9470612310
2018-07-03·BA00·III·en·02
Technical Data
13
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Digital Input Output Module for Zone 1
Series 9470/32
Auxiliary power
Version
Intrinsically safe Ex ia via BusRail
Max. current
consumption
120 mA
Max. power
consumption
2.5 W
Max. power
dissipation
2.5 W
Device-specific data
Settings
Module
Diagnostics
message
ON / OFF
Signal
Signal type
Input / output*)
Pulse
extension /
frequency filter
0 s / off; 0.6 s / small; 1.2 s / medium; 2.4 s / large *)
Inverting
input/output
normal / inverted*)
Line fault
monitoring
ON / OFF
Behaviour in
case of error
Replacement value '0';
replacement value '1';
hold (initial value 0);
hold (initial value 1)
Operating mode
counter/
frequency
Counter 16 bit; 0.1 ... 600 Hz; 1 Hz ... 3 kHz; 1 Hz ... 20 kHz;
1 Hz ... 20 kHz with direction; up/down counter 16 bit; up/down counter 32 bit*)
Counter control Run, Stop, Reset
Counting event positive slope; negative slope*)
*) setting is made for channel pairs
Ambient conditions
Ambient temperature -40 … +75 °C
Storage temperature -40 ... +80 °C
Maximum relative
humidity
95 % (without condensation)
Use at the height of
< 2000 m
Semi-sinusoidal
shock
(IEC EN 60068-2-27)
15 g (3 shocks per axis and direction)
Sinusoidal vibration
(IEC EN 60068-2-6)
1 g in the frequency range 10 ... 500 Hz
2 g in the frequency range 45 ... 100 Hz
Technical Data
Summary of Contents for 9470/32 Series
Page 49: ......