Engineering
16
218129 / 9470612310
2018-07-03·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Digital Input Output Module for Zone 1
Series 9470/32
6.2
"Frequency" or "Counter" Operating Mode
In the "Counter with direction" or "Frequency with direction" operating mode, two adjacent
channels are operated together. Thereby, the following channel assignment applies:
• First channel (8, 10, 12, 14) = signal value (1 or 0)
• Second channel (9, 11, 13, 15) = direction (0 = forward, 1 = backward)
15340E00
6.3
IS1+ Compatible Low Power Actuators
Optionally, non-used channels with resistors (single electrical equipment for
intrinsically safe circuits according to EN 60079-11) can be equipped in order
to suppress the error messages of the respective channels.
(Resistors are available as accessories!)
For the "Frequency" or "Counter" operating mode only channels 8 to 15 are
used.
Manufacturer
Actuator
Type
Version
Herion
Low power valve
Type 2085
6 V
ASCO / Joucomatic
Piezo valve
Nr.63000059
6 V
Piezo valve
Nr.63000060
6 V
Piezo valve
Nr.63000061
6 V
Piezo valve
Nr.63000062
6 V
Samson
Limit signal transmitter
Type 3776
6 V
Solenoid valve
Type 3701
6 V
Limit signal transmitter
Type 3775
6 V
Solenoid valve
Type 3962
6 V
Solenoid valve
Type 3963
6 V
Positioner
Type 3766
6 V
Festo (Seitz)
Solenoid valve
PV12 F73 Xio H
6.4 V
R. Stahl Schaltgeräte
LED indicator lamp
8010/C1661
3 V
0
forwards
1
backwards
Direction
ch 1
ch 1
Sensor 1
Sensor 2
Direction