9470 6 031 001 1
1 of 1
2016
03.03. Bagusch
Kaiser
Digital Input Output Module
Type 9470/32-16-1*
01 09.03.2018 Bagusch
Nonhazardous
Class I, II, III, Division 1, Group A-G
or Class I, Zone 1, Group IIC/IIB
Hazardous (Classified) Locations
NAMUR Signal < 1.2 / > 2.1 mA
Approved NAMUR proximity switches,
optocouplers, low power valves
Wiring legend
Connection allocation
– Digital Input Output Module Type 9470/32
X1
X2
channel 0
1(+), 2(-)
channel 8
17(+), 18(-)
channel 1
3(+), 4(-)
channel 9
19(+), 20(-)
channel 2
5(+), 6(-)
channel 10
21(+), 22(-)
channel 3
7(+), 8(-)
channel 11
23(+), 24(-)
channel 4
9(+), 10(-)
channel 12
25(+), 26(-)
channel 5
11(+), 12(-)
channel 13
27(+), 28(-)
channel 6
13(+), 14(-)
channel 14
29(+), 30(-)
channel 7
15(+), 16(-)
channel 15
31(+), 32(-)
Notes:
1.
Intrinsically safe apparatus shall be switches or an Approved
System or Entity device connected in accordance with the
manufacturer´s installation instructions.
2.
For Entity concept use the appropriate parameters from
above to ensure the following:
V
OC
or V
t
V
max
C
a
C
i
+ C
leads
I
SC
or I
t
I
max
L
a
L
i
+ L
leads
3.
The values of La and Ca in the tables on the right side are the
maximum values for combined inductance and capacitance
(including cable inductance and capacitance). The values for La
and Ca marked in grey are the values determined according to
curves and tables of IEC 60079-11, Annex A. These grey marked
values may be used for assessment as per IEC 60079-14,
intrinsically safe circuits with only one source of power.
4.
Suitable separation must be maintained between wiring of each
I.S. input channel.
5.
For Installation in Division 1 or Zone 1 see Certification drawing
for IS1 resp. IS1+ Remote I/O System No. 9400 6 031 003 1 as
part of the documentation of the CPU & Power Modules.
6.
For Installation in Division 2 or Zone 2 see Certification drawing
for IS1 resp. IS1+ Remote I/O System No. 9400 6 031 004 1 or
9400 6 031 006 1 as part of the documentation of the CPU &
Power Modules.
7.
Installation in Division 2 or Zone 2 is also allowed according to
NEC Article 504/505 or Canadian Electrical Code, CSA C22.
The Type 9470 Digital Input Output Module is designed to receive up
to 16 discrete input signals from dry contacts and NAMUR proximity
sensors etc. and transmit them to the IS1 CPU & Power Module. It is
also possible to drive low power valves. The module is intrinsically
safe for installation in a Class I, II, III, Division 1, Group A-G or Class I,
Zone 1, Group IIC/IIB hazardous location according to NEC Article
504/505 or Canadian Electrical Code, CSA C22; Providing intrinsically
safe connections for Class I, Division 1, Groups A-G or Class I, Zone
0, Group IIC/IIB hazardous locations listed below.
Entity parameters for wiring configuration to the left are as follows:
CL I, DIV 1, A,B /
Zone 0, GP IIC
CL I, DIV 1, C-G /
Zone 0, GP IIB/IIIC
La [mH]
Ca [µF]
La [mH]
Ca [µF]
single channel
280
-
1000
-
100
0.49
100
2.6
V
OC
= 9.8 V
50
0.56
50
2.8
I
SC
= 10.4 mA
20
0.64
20
3.3
P
O
= 25.5 mW
10
0.72
10
3.7
Ci
= 2.5 nF
5
0.81
5
4.2
Li
= 0 mH
2
0.96
2
5.1
1
1.1
1
6.0
0.5
1.3
0.5
7.2
0.2
1.6
0.2
9.3
0.1
2.0
0.1
12.0
0.02
3.3
0.01
23.0
2 ch. connected parallel
-
-
270
-
100
0.3
100
2.3
V
OC
=
9.8 V
50
0.44
50
2.6
I
SC
=
20.8 mA
20
0.57
20
3.1
P
O
=
51.0 mW
10
0.67
10
3.6
Ci
=
5 nF
5
0.77
5
4.1
Li
=
0 mH
2
0.93
2
5.1
1
1.1
1
6.0
0.5
1.3
0.5
7.2
0.2
1.6
0.2
9.3
0.1
2.0
0.1
12.0
0.02
3.3
0.01
23.0
4 ch. connected parallel
-
100
1.5
27
0.32
50
2.1
V
OC
=
9.8 V
20
0.41
20
2.8
I
SC
=
41.6 mA
10
0.56
10
3.4
P
O
=
102.0 mW
5
0.69
5
3.9
Ci
=
10 nF
2
0.88
2
4.9
Li
=
0 mH
1
1.0
1
5.9
0.5
1.2
0.5
7.1
0.2
1.6
0.2
9.3
0.1
2.0
0.1
12.0
0.01
3.3
0.01
23.0
8 ch. connected parallel
-
-
29
1.7
-
-
20
2.1
V
OC
=
9.8 V
6.7
0.4
10
2.9
I
SC
=
83.2 mA
5
0.5
5
3.6
P
O
=
204.0 mW
2
0.76
2
4.7
Ci
=
20 nF
1
0.96
1
5.7
Li
=
0 mH
0.5
1.2
0.5
6.9
0.2
1.6
0.2
9.1
0.1
1.9
0.1
11
0.01
3.3
0.01
23
16 ch. connected parallel
-
-
7.7
2.1
-
-
5
2.8
V
OC
=
9.8 V
1.8
0.53
2
4.2
I
SC
=
164 mA
1
0.77
1
5.3
P
O
=
402 mW
0.5
1.0
0.5
6.6
Ci
=
40 nF
0.2
1.5
0.2
8.9
Li
=
0 mH
0.1
1.8
0.1
11
0.01
3.3
0.01
23