Function and Device Design
8
218129 / 9470612310
2018-07-03·BA00·III·en·02
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Digital Input Output Module for Zone 1
Series 9470/32
4.1
Function
Application range
The digital input output module is used for connecting up to 16 intrinsically safe digital
signals to the IS1 Remote I/O system.
It is approved for use in hazardous areas of Zones 1, 2, 21 and 22 and in safe areas.
Mode of operation
All channels can be parameterised in pairs as input for connection of passive contacts or
NAMUR proximity switches (EN 60947-5-6) or as output for connection of low power
solenoid valves. Up to 8 inputs can be used as frequency inputs or counters up to 20 kHz,
in the "Rotation direction recognition" and "Forward/backward counter" operating mode
up to 4 inputs. The Ex i inputs or outputs are short-circuit proof and galvanically separated
from the system.
4.2
Device Design
The type 9470/32 digital input output module is a compatible replacement for
series 9470/12, 9470/22 and 9475/12-08-41 IS1 Remote I/O modules.
#
Device component
Description
11919E00
1
Cover flap
Cover flap with insert label (open) and
connection diagram
2
Labelling
Module data
(serial number, hardware revision number,
software revision number, date of manufacture,
e.g.: 123456DE9999 Rev.A 01-01 0508)
3
LEDs
LEDs (red) for error indication
(wire breakage/short circuit) for each channel;
LEDs (yellow) for status indication (ON/OFF) for
each channel
4
Notch lever
Notch lever for removing the module from the
BusRail
5
LED
LED for indication of operation ("RUN", green),
error ("ERR", red) and maintenance ("M/S", blue)
(for further information, see "Indication" chapter)
6
Terminal
Pluggable terminal X2 with two safety screws
7
Terminal
Pluggable terminal X1 with two safety screws
1
2
3
4
7
5
6
Summary of Contents for 9470/32 Series