Page | 35
5.2 Nominal UPS Output Current
Model
Output Voltage
120
1
208
220
230
240
6KVA
25
29
27
26
25
10KVA
42
48
45
43
42
NOTE 1:
Current listed is for each 120V output
5.3 Recommended Wiring
Model
Wiring spec (AWG)
1,2
Input
Output
120V
208V
220V
230V
240V
6KVA
8
10
10
10
10
10
10KVA
6
8
8
8
8
8
NOTE 1:
It is recommended to use 75°C copper wire.
NOTE 2:
Recommended cable sized based on THW cables at 30°C ambient (NEC Table 310.16)
.
If
different cables are used or installed at higher ambient, the cable size need to be reviewed.
NOTE 3:
10 lb-in torque force when connecting to input/output terminal block for 6KVA models.
NOTE 4:
18 lb-in torque force when connecting to input/output terminal block for 10KVA models.
NOTE 5:
External battery wires use reinforced insulation or double insulated wire.
5.4 Agency Listings
Safety
Safety Conformance: IEC/EN 62040-1,UL1778 (4th Edition)
Safety Markings : UL, CE
EMI
Conducted Emission.....................:IEC/EN 62040-2,FCC Part 15 Class A
Radiated Emission........................:IEC/EN 62040-2,FCC Part 15 Class A
EMS
ESD.............................................. :IEC/EN 61000-4-2, Level 4
RS.................................................:IEC/EN 61000-4-3, Level 3
EFT.............................................. :IEC/EN 61000-4-4, Level 4
SURGE........................................ :IEC/EN 61000-4-5, Level 4
CS................................................ :IEC/EN 61000-4-6, Level 3
Power-frequency Magnetic field...:IEC/EN 61000-4-8, Level 4
Low Frequency Signals................:IEC/EN 61000-2-2
6. Storage
Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
Recharge Frequency
Charging Duration
-25°C - 40°C (-13°F - 104°F)
Every 3 months
1-2 hours
40°C - 45°C (104°F - 113°F)
Every 2 months
1-2 hours
See Staco’s website for warranty details:
http://www.stacoenergy.com/support/literature-download-center.html