DocID022729 Rev 5
43/70
L6472
Programming manual
70
In order to convert the DEC value in step/s2 the following formula can be used:
Equation 3
where DEC is the integer number stored in the register and tick is 250 ns.
The available range is from 14.55 to 59590 step/s
2
with a resolution of 14.55 step/s
2
.
Any attempt to write the register when the motor is running causes the command to be
ignored and the NOTPERF_CMD flag to rise (see
9.1.7 MAX_SPEED
The MAX_SPEED register contains the speed profile maximum speed expressed in
step/tick (format unsigned fixed point 0.18).
In order to convert it in step/s the following formula can be used:
Equation 4
where MAX_SPEED is the integer number stored in the register and tick is 250 ns.
The available range is from 15.25 to 15610 step/s with a resolution of 15.25 step/s.
9.1.8 MIN_SPEED
The MIN_SPEED register contains the following parameters:
The MIN_SPEED parameter contains the speed profile minimum speed. Its value is
expressed in step/tick and to convert it in step/s the following formula can be used:
Equation 5
where MIN_SPEED is the integer number stored in the register and tick is the ramp 250 ns.
The available range is from 0 to 976.3 step/s with a resolution of 0.238 step/s.
Any attempt to write the register when the motor is running causes the NOTPERF_CMD flag
to rise.
step s
DEC 2
40
–
tick
2
-----------------------------
=
step s
MAXSPEED 2
18
–
tick
---------------------------------------------------
=
Table 11. MIN_SPEED register
Bit12 Bit 11 Bit 10 Bit 9
Bit 8
Bit 7
Bit 6
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 MIN_SPEED
step s
MINSPEED 2
24
–
tick
-------------------------------------------------
=