6  Configuration
SIM 740-... 

Configuration of SIM 740-...

Programming the SIM 740-... takes 
place using a connected PC via 
PRI 602-... USB and SIVS 610-...
The SIM 740-... is selected in 
the configuration software 
DCIP CO 600-... The SIM 740-... 
can be used in two operating modes 
(camera assignment and monitor 
assignment). The operating mode 
depends on the application and the 
system topology.
The required operating mode is 
selected in the first mask. 

Basic parameters

Master monitor address

This address is one of the addresses 
which can be selected under the 
next tab (SIM addresses). Using this 
address, the SIM 740-... can be 
accessed for servicing purposes. If 
there are several SIM 740-... units 
in a Multi system, ensure that each 
SIM 740-... is given a different 
master monitor address.

Speech channels

Select the installed speech channel. 
Please note: 
In group systems, speech channel 2 
must be switched off.

Upgrade stage

In stage 1, address area from 
1 - 254, only speech channel 1 and 
2 are allowed. Application in older 
systems, e.g. with HT 641/642/643.
In step 2, address area from 1 - 500, 
speech channel 1 and 2, or speech 
channel 1 and the group speech 
channel are allowed. 
For current applications, e.g. with 
HT 740-..., HT 840-...

SIM addresses

In the mask SIM addresses, the 
physical Multi bus addresses are 
selected under which you wish to be 
able to reach the SIM 740-... or the 
relevant PC users.
The master monitor address is 
already entered. 
The DCIP Software Client is the 
PC on which a Siedle in-house 
telephone is depicted by the 
software.
When using the “monitor 
assignment” mode, 3 additional 
addresses can be selected. 
When using the camera assignment 
mode, 48 additional addresses can 
be selected.

The functions 1 - 256 correspond to 
the virtual buttons 1 - 256.

Each of these functions (buttons) 
can be assigned a command.

Functions

In the Functions mask, only remote 
switching functions can be assigned. 
Parameters 1-9 correspond to the 
remote switching functions 1-9 on 
the Multi bus. In the Multi system 
various devices can be programmed 
for this remote switching function 
in order to initiate an action. (e.g. 
FSM 740-...)
The functions 10 - 256 are intended 
for future applications. 

Messages

In the Messages mask, status 
messages are configured which are 
displayed in the Software Client. In 
the Multi system, status messages 
1-8 exist in addition.
The statuses ON and OFF are 
transferred. Each of these messages 
can be assigned to an individual text. 

Free text input

 

Display of texts at the Software-
Client. 
Example Display of three statuses in 
the Software-Client.
Messages in the Multi system are 
only transmitted when a status is 
changed.
After power ON, the status is 
unknown. In this case, the status 
„Not initialised“ is displayed at the 
Software Client. Only when the 
status is changed for the first time is 
the current status displayed.

Summary of Contents for DCIP 740-0

Page 1: ...Manual DoorCom IP DCIP 740 0...

Page 2: ...Software 11 Siedle Multi 12 5 Installation Wiring diagrams DCIP 740 0 Terminals DCIP 740 0 14 LED display SIVS 610 15 Block diagrams 16 Wiring diagram Siedle Multi 17 6 Commissioning DCIP 740 20 SIM...

Page 3: ...building installation with a contact opening of at least 3 mm Ensure that the connection point in the building installation is fused with max 16 A When planning the required distributor space for swit...

Page 4: ...4 call destinations i e Siedle Multi system addresses can be assigned to the interface SIM 740 These correspond to the functions of the 4 Multi telephones The call destination can be dialled from eve...

Page 5: ...levant product information and programming instructions of the manufacturer Mounting and installation The DCIP 740 can be connected at any optional point of the Siedle Multi system bus The devices are...

Page 6: ...ample comprising two groups and five individual clients with each group and each individual client occupying one address Consequent ly a total of seven addresses are used in the system Group 1 20 PC u...

Page 7: ...a protocol arriving at the router are analysed for information and forwarded or routed to the intended destination network RS232 Designation for a serial interface for instance the COM interface of a...

Page 8: ...tion 25 mA per call button module TM 612 Used as call buttons 1 4 directly at the SIVS 600 TME 645 0 Call button module extension with interface to the Vario bus for max 8 TME 645 Suitable for connect...

Page 9: ...abetical input module with keypad A I Input unit for alphanumerical selection of PC users For use in Siedle Multi systems only in conjunction with the TLC 640 02 COM 611 01 DIM 640 0 and SIVS 600 Oper...

Page 10: ...red for configuration of the system interface video server with software DCIP CO 600 version 1 1 or higher IPVS 600 0 System interface video server Processing and adjustment of audio and video transmi...

Page 11: ...iguration software PC program for set up and programming of the Siedle interface video server SIVS 610 Programming takes place via the USB programming interface PRI 602 USB configuration software vers...

Page 12: ...s able to simulate several Multi telephones depending on the operating mode Only one of these virtual telephones can ever be active at one time i e conduct a call Dimensions 107 x 89 x 60 mm VMS 641 0...

Page 13: ...loudspeaker for camera on With DoorCom IP the contact is permanently active Potential is switched via the UPS terminal VKA Actuation of camera distributor M is switched A1 A1 Potential free contact f...

Page 14: ...ghts up in green with an existing network connection g LED T flashes orange on data transmission via the network Terminals IPVS 600 0 h Video input 1Vss from the SIVS 610 i Audio Line In to the SIVS 6...

Page 15: ...ive possibly new software update or exchange ON Slow flashing Variobus address error error remedy possible on site ON Fast flashing The 15 V power supply terminal bv cv is overloaded Error remedy poss...

Page 16: ...s Supply voltage 24 V DC T not used DR via T TLC 640 02 Li not used USP Universal Serial Port SN1 RF signal path SN2 SIM 740 SIVS 610 n1 RF signal for n2 connected DCA 740 01 Block diagram SIM 740 0 S...

Page 17: ...17 Monitor assignment mode 5 Installation DCIP 740 Siedle multi Siedle Multi requires additional supply devices which are not listed in this wiring diagram...

Page 18: ...18 5 Installation DCIP 740 Siedle multi Camera assignment mode Siedle Multi requires additional supply devices which are not listed in this wiring diagram...

Page 19: ...small number of doors and a large number of PC users Monitor assignment mode Up to a maximum of 4 call destinations i e Siedle Multi system addresses can be assigned to the interface These correspond...

Page 20: ...alled on the PC users in the network Import of the generated file dcip Selection of addresses to be signalled on the affected PC user Step 1 Issue of the IP address and subnet mask in the IPVS 600 The...

Page 21: ...h to be able to reach the SIM 740 or the relevant PC users The master monitor address is already entered The DCIP Software Client is the PC on which a Siedle in house telephone is depicted by the soft...

Page 22: ...parately in each IPVS 600 Multicast address video 1 For each IPVS 600 enter a multicast address which you wish to operate in the multicast mode duplication of the data streams in the network With the...

Page 23: ...23...

Page 24: ...rements for the configuration software PC with Intel Pentium III from 1 GHz or comparable processor at least 256 MB RAM min 25 MB hard disk memory Serial COM interface RS232 or serial USB adapter CD R...

Page 25: ...the configuration to the SIM 740 with Send configuration Below entries are details of the SIM 740 and the SIVS 610 synchronized There is also the associated phone number given System initialization on...

Page 26: ...are Client The Software Client configuration can be opened by pressing the right hand mouse button on the virtual in house telephone In the first tab Configuration select add DCIP SC file and import t...

Page 27: ...ff If there is an active firewall the application file DCIP SC 600 0 exe must be defined as an exception or as a permanently authorized program application In order to establish a video link it may be...

Page 28: ...ction SW1 OFF 0 dB as delivered status ON 9 dB Level adjustment TLM 645 Setting the volume of the PC user from the door station in the direction of the PC user Establish the connection to the PC At th...

Page 29: ...be switched off If the number 61 is pressed the door release is actuated for 3 seconds For connection of more than one telephone a so called group call or collective call function must be set up in th...

Page 30: ...this to 32 MB this problem occurs primarily with laptops Set the hardware acceleration of the graphics card display to max Speech goes from the PC only in the direction of the door Enter the software...

Page 31: ...31...

Page 32: ...d using a digital multimeter Idle status min max Voltage at line rectifier NG 608 24 V DC 28 5 V DC Voltage b c at SIVS 610 15 V DC Voltage Da Db at SIVS 610 0 3 V DC Speech mode Voltage M at CMC 612...

Page 33: ...laims to damages Connection 17 As delivered status 29 Block diagram 13 Camera assignment 4 6 Client 6 26 Commissioning 20 Config 20 Cross over 20 DoorCom 10 Factory setting 29 Full duplex 6 HTTP 6 IP...

Page 34: ...2007 02 09 Printed in Germany Order no 0 1101 037156 EN S Siedle S hne Postfach 1155 D 78113 Furtwangen Bregstra e 1 D 78120 Furtwangen Tel 49 7723 63 0 Fax 49 7723 63 300 www siedle de info siedle de...

Reviews: