NO. Parameter name
allow
adjustment
Settings
(
default
)
Description
ENA
After the power saving mode is
enabled, if the load is null or less than
50W, the inverter output is turned off
after a delay for a certain period of
time. When the load is more than
50W, the inverter automatic restart.
[23]
Restart when over
load
DIS
Automatic restart when overload is
disabled. If an overload occurs and
the output is turned off, the machine
will not restart.
ENA
Automatic restart when overload is
enabled. If an overload occurs and
the output is turned off, the machine
will restart after a delay of 3 minutes.
After it reaches 5 cumulative times,
the machine will not restart.
[24]
Restart when over
temperature
[24] DIS
Automatic restart when over
temperature is disabled. If an over-
temperature shutdown occurs,
machine will not restart to turn the
output on.
ENA
Automatic restart when over
temperature is enabled. If an over-
temperature shutdown occurs, the
machine will restart when the
temperature drops.
[25]
Alarm enable
DIS
Alarm is disabled
ENA
Alarm is enabled
[26]
Beeps while
primary source is
interrupted
DIS
Alarm beep is disabled when the
status of the main input source
changes
ENA
Alarm beep is enabled when the
status of the main input source
changes
[27]
Bypass output
DIS
It is disabled to automatically switch