Installation Completion
Installation of the CSM-C Compact Steam Generator is now complete.
Commissioning
After all installation procedures have been completed, and all clean steam, feed water,
energy source, pneumatic joints, and power connections have been double checked, the
unit is ready for commissioning.
Commissioning Procedure
Commissioning may now be carried out in accordance with the following procedure.
NB: It is recommended that this procedure is always carried out with the presence of a
qualified Spirax Sarco engineer.
Installation Inspection
1. Ensure that unit has been installed in line with Spirax Sarco recommendations.
2. Ensure the blow down line and safety valve line are piped away to a safe location.
3. Ensure All Isolation Valves are closed (Primary Steam supply, Clean steam outlet,
Feed Water inlet, Pneumatic supply, Condensate).
Pre-Commissioning Inspection
4. Check all joints within the generator are tight.
5. Note Orientation of the feedtank level transducer (should be horizontal).
6. Check the Electrical connections.
7. Check Supply Voltage is correct.
8. Check Pneumatic supply is correct.
Configuration parameters
To do this operation please consider the PLC control unit manual at the paragraph
“Protected Parameters”.
Manual Operation
Once completed the configuration steps, go on the manual check of the steam Generator
To do this operation please consider the PLC control unit manual at the paragraph “Manual
operations”.
Notes
Durning the manual cycle check the correct rotation of the pump, and that is no cavitation.
In case that the direction of the rotation is no correct switch off the panel and invert two
of the three supply phases of the pump.
In presence of pump cavitation perform purging. Please refers to the instruction manual
pump in chapter 6.
Automatic Operation
To do this operation please consider the PLC control unit manual at the paragraph “Auto
operations”.