05 INSTALLATION
Optional: Integration of Xcontrol-P
There is the possibility to integrate the Xcontrol-P pneumatic control system into the Xcontrol-E. This means that
the 24 V from the Xcontrol-E can be used for switching the valve. In addition, the pressure switch of the Xcontrol-
P can be integrated into the safety circuit so that the emergency stop can be activated, and the spindle stopped
if the pressure falls below the required level.
For integration of the valve see wiring diagram below:
The connection cable of the Xcontrol-P needs to be inserted into the Xcontrol-E. Pin 1 of the cable must be
inserted to terminal X1:38 (upper row), Pin 2 to X1:52 (lower row). For activating the valve, a switch between
terminal X1:44 (lower row) and X1:38 (lower row) can be integrated.
For integration of the Xcontrol-P pressure switch see wiring diagram below:
Pin 3 of the Xcontrol-P connection cable must be inserted to terminal X1:58 (upper row) and Pin 4 to terminal
X1:59 (lower row). Therefore, the bridge between X1:58 and X1:59 must be removed.