Chapter 3: Configuring the 1762sc-IF4OF4 for RSLogix 500
3-11
User’s Manual Pub. 0300247-01 Rev. D
Outputs:
Open circuit detection is available for output channels in current
mode. For current outputs, open wire may not be detected when the
output is driven at or near zero.
NOTE
Input word 3 will always display the raw CJC temperature in degrees C,
Engineering units, and so no channel configuration is needed.
Section 3.6
Module
Update Time
The module update time is determined by the number of input channels enabled
and by the filter frequency selected for each channel.
ADC Filter
Frequency
Filter
Frequency
(-3 dB point)
Conversion
Time
Module update
470 Hz
109 Hz
20 ms
= sum of
conversion times
for each enabled
channel
62 Hz
14 Hz
45 ms
17 Hz
4 Hz
135 ms
4 Hz
1 Hz
495 ms
Getting Technical
Assistance
Note that your module contains electronic components which are susceptible to
damage from electrostatic discharge (ESD). An electrostatic charge can
accumulate on the surface of ordinary plastic wrapping or cushioning material
.
In the unlikely event that the module should need to be returned to
Spectrum Controls, Inc., please ensure that the unit is enclosed in approved
ESD packaging (such as static-shielding / metalized bag or black conductive
container).
Spectrum Controls, Inc. reserves the right to void the warranty on any unit that is
improperly packaged for shipment.
RMA (Return Merchandise Authorization) form required for all product
returns.
For further information or assistance, please contact your local distributor, or call
the Spectrum Controls Technical Support at:
USA - 425-746-9481
Declaration of
Conformity
Available upon request
Summary of Contents for 1762sc-IF4OF4
Page 1: ......
Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Page 44: ...User s Manual Pub 0300247 01 Rev D...