1-2
Chapter 1: Module Overview
User’s Manual Pub. 0300247-01 Rev. D
NOTE
Channel 0 through 3 can be configured for voltage or current and support
voltage and current ranges defined in Table 1-1. The module is shipped
with channels 6 and 7 in current mode (DIP switches inside unit both
down as shown below). The channel
1
switch below is associated with
module channel
6
, and channel switch
2
is associated with module channel
7
. Move each switch to the up position to achieve voltage input for each
respective channel. Refer to Figure 1-1 to view DIP switch location (item
10).
Section 1.3
Input Types
and Ranges
The table below lists the input types and their associated ranges.
Table 1-2 (Input Types)
Input Type
Range
E Type Thermocouple -200 to 1000 ˚C (-328 to 1832 ˚F)
J Type Thermocouple -180 to 1200 ˚C (-292 to 2192 ˚F)
K Type Thermocouple -200 to 1370 ˚C (-328 to 2498 ˚F)
T Type Thermocouple -190 to 400 ˚C (-310 to 752 ˚F)
Voltage
0 to 5 V (0 to 5.5 V)
1 to 5 V (0 to 5.5 V)
±10 V (-11 to +11 V)
0 to 10 V (0 to 11 V)
Current
4 to 20 mA (3.92 to 20.4 mA)
0 to 20 mA (0 to 20.4 mA)
NOTE
Channels 4 and 5 can be configured for current inputs only, and support
current input ranges as shown in Table 1-2.
NOTE
Channels 6 and 7 can be configured for either current or voltage inputs.
Current support includes input ranges as shown in Table 1-2. Voltage
input ranges include both thermocouple and voltages as defined in Table
1-2.
Summary of Contents for 1762sc-IF4OF4
Page 1: ......
Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Page 44: ...User s Manual Pub 0300247 01 Rev D...