Table 3-1 (Output File)
Register
Function
Output File (Used for Module Configuration)
O:e.0
Channel 0 Data Word
O:e.1
Channel 1 Data Word
O:e.2
Channel 2 Data Word
O:e.3
Channel 3 Data Word
O:e.4
Low byte: Channel 0 Configuration Register (Output)
1
High byte: Channel 1 Configuration Register (Output)
1
O:e.5
Low byte: Channel 2 Configuration Register (Output)
1
High byte: Channel 3 Configuration Register (Output)
1
O:e.6
Low byte: Channel 4 Configuration Register (Input)
2
High byte: Channel 5 Configuration Register (Input)
2
O:e.7
Low byte: Channel 6 Configuration Register (Input)
3
High byte: Channel 7 Configuration Register (Input)
3
1
See
Table 3-2
,
2
See
Table
3-4
,
3
See
Table 3-5
3.4.2
Output Channel Configuration (Channels 0 through 3)
The table below describes the configuration options for analog output channels 0
through 3.
Table 3-2 (Configuration for Output Channels 0 through 3)
To Select
Make these bit settings
7
6
5 4 3 2 1 0
Output Type
4 to 20 mA
0 0 0
0 to 20 mA
0 0 1
-10 to 10 V
0 1 0
0 to 10 V
0 1 1
1 to 5 V
1 0 0
0 to 5 V
1 0 1
Reserved
1 1 0
Channel Disabled
1 1 1
Data Format
Scaled for PID
0 0
Engineering Units
0 1
Percent Range
1 0
Raw/Proportional Data
1 1
Unused
0
0
0
Summary of Contents for 1762sc-IF4OF4
Page 1: ......
Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Page 44: ...User s Manual Pub 0300247 01 Rev D...