Chapter 1: Module Overview
1-3
User’s Manual Pub. 0300247-01 Rev. D
Section 1.4
Data Formats
For input channels, the data can be configured for:
Engineering units ×1
Engineering units ×10
Scaled-for-PID
Raw/proportional data
For output channels, the data can be configured for:
Engineering units
Scaled for PID
Raw/proportional data
Percent range
Section 1.5
Filter
Frequencies
For input channels, the module uses a digital filter that provides high frequency
noise rejection for each input signal. The filter for each channel is programmable
allowing you to select from four different filter frequencies:
4 Hz
17 Hz
62 Hz
470 Hz
Section 1.6
Hardware
Features
Channels are wired as differential inputs or single-ended outputs. One cold
junction compensation (CJC) sensor comes installed under the terminal block
(and is not accessible to the user) to enable accurate readings when using
thermocouple input types. The CJC sensor compensates for offset voltages
introduced into the input signal as a result of the cold junction where the
thermocouple wires come into contact with the terminal block.
Module configuration is done via the controller’s programming software. The
module configuration is stored in the memory of the controller. Refer to your
controller’s user manual for more information. The illustration below shows the
module’s hardware features.
Summary of Contents for 1762sc-IF4OF4
Page 1: ......
Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Page 44: ...User s Manual Pub 0300247 01 Rev D...