Chapter 3: Configuring the 1762sc-IF4OF4 for RSLogix 500
3-5
User’s Manual Pub. 0300247-01 Rev. D
Table 3-3 lists the number of counts for each of the supported input channel data
ranges.
Table 3-3 (Output Channel Data Ranges)
Output
Range
Output Value Condition
Raw/Prop EU
PID
% FS
4..20 mA
20.40 mA
High Limit
32767
20400 16793 10250
20.00 mA
High Range 31176
20000 16383 10000
4.00 mA
Low Range
-32450
4000
0
0
3.92 mA
Low Limit
-32768
3920
-82
-50
0..20 mA
20.40 mA
High Limit
32767
20400 16711 10200
20.00 mA
High Range 31482
20000 16383 10000
0.00 mA
Low
Limit/Range
-32768
0
0
0
+/-10 V
11.00 VDC
High Limit
32767
11000 17202 11000
10.00 VDC
High Range 29788
10000 16383 10000
-10.00 VDC
Low Range
-29788
-10000 0
-10000
-11.00 VDC
Low Limit
-32768
-11000 -819
-11000
0 to 5 V
5.50 VDC
High Limit
32767
5500
18021 11000
5.00 VDC
High Range 26809
5000
16383 10000
0.00 VDC
Low Range
-32768
0
0
0
0.00 VDC
Low Limit
-32768
0
0
0
0 to 10 V
11.00 VDC
High Limit
32767
11000 18021 11000
10.00 VDC
High Range 26809
10000 16383 10000
0.00 VDC
Low Range
-32768
0
0
0
0.00 VDC
Low Limit
-32768
0
0
0
1 to 5 V
5.50 VDC
High Limit
32767
5500
18431 11250
5.00 VDC
High Range 26809
5000
16383 10000
1.00 VDC
Low Range
-20853
1000
0
0
0.00 VDC
Low Limit
-32768
000
-4096 -2500
3.4.3
Input Channel Configuration (Channels 4 and 5)
Channels 4 and 5 are current only channels. The table below describes the
configuration options for channels 4 and 5.
Summary of Contents for 1762sc-IF4OF4
Page 1: ......
Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Page 44: ...User s Manual Pub 0300247 01 Rev D...