Chapter 3: Configuring the 1762sc-IF4OF4 for RSLogix 500
3-7
User’s Manual Pub. 0300247-01 Rev. D
To Select
Make these bit settings
7 6 5 4 3 2 1 0
0 to 5 V
0 1 0 1
Type J TC
0 1 1 0
Type K TC
0 1 1 1
Type E TC
1 0 0 0
Type T TC
1 0 0 1
Type J TC CJC Disabled
1 0 1 0
Type K TC CJC Disabled
1 0 1 1
Type E TC CJC Disabled
1 1 0 0
Type T TC CJC Disabled
1 1 0 1
Display CJC channel temp
1 1 1 0
Channel Disabled
1 1 1 1
Table 3-6 lists the number of counts for each of the supported input channel data
ranges.
NOTE
The engineering unit data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional
counts, scaled-for-PID and percent of full-scale data formats may yield the
highest effective resolutions, but may also require that you convert
channel data to real engineering units in your control program.
Table 3-6 (Input Channel Data Ranges)
Input Range
Input Value
Condition
EU ×1
EU ×10
Raw
Prop
PID
J Thermocouple
1200.00 °C
High Limit
12000
1200
32767
16383
1200.00 °C
High Range
12000
1200
32767
16383
-180.00 °C
Low Range
-1800
-180
-32768
0
-180.00 °C
Low Limit
-1800
-180
-32768
0
K
Thermocouple
1370.00 °C
High Limit
13700
1370
32767
16383
1370.00 °C
High Range
13700
1370
32767
16383
-200.00 °C
Low Range
-2000
-200
-32768
0
-200.00 °C
Low Limit
-2000
-200
-32768
0
E Thermocouple
1000.00 °C
High Limit
10000
1000
32767
16383
1000.00 °C
High Range
10000
1000
32767
16383
-200.00 °C
Low Range
-2000
-200
-32768
0
-200.00 °C
Low Limit
-2000
-200
-32768
0
T Thermocouple
400.00 °C
High Limit
4000
400
32767
16383
400.00 °C
High Range
4000
400
32767
16383
-190.00 °C
Low Range
-1900
-190
-32768
0
Summary of Contents for 1762sc-IF4OF4
Page 1: ......
Page 6: ...vi MicroLogix 1200 Analog Combo Module 4Ch IN 4Ch Out User s Manual Pub 0300247 01 Rev D...
Page 41: ...Appendix A Module Specifications A 7 User s Manual Pub 0300247 01 Rev D...
Page 42: ...A 8 Appendix A Module Specifications User s Manual Pub 0300247 01 Rev D...
Page 44: ...User s Manual Pub 0300247 01 Rev D...