Revised Date: 2018/04/24
14
E14
ESI
ESI Contact Definition
0
0~1
0
0~1
0: N.O.
1: N.C.
E15
rS
Present Temperature Is Getting
from Built-In Temperature
Sensor, or Remote Temperature
Sensor.
0
0~1
0
0~1
0: built-in
1: remote
E16
-SP-
Display Present Value of
Temperature or Set-Point for
Normal Displaying
0
0-1
0
0-1
0: display PV
1: display SP
E17
FAnL
Lowest Fan Speed in Continuous
Fan Mode
25
0~100
25
0~100
1(%)
E18
Fan2
Medium Fan Speed
60
20~100
60
20~100 1(%)
E19
dLAy
Minimum delay time between
cooling and heating
0
0~5
0
0~5
1 (minute)
E20
dirC
Cooling Valve N.C./ N.O. Setting
1
0~1
1
0~1
0: N.O.
1: N.C.
E21
dirH
Heating Valve N.C./ N.O. Setting
1
0~1
0
0~1
0: N.O.
1: N.C.
E22
dbOP
Deadband Options
1
0~1
1
0~1
0: DB is
aligned to
Cooling SP
1: SP is in the
middle of DB
E23
tESt
Self-Diagnostic
E24
rSt
Reset All Parameters to Factory
Defaults
E25
End
Exit Engineer Mode