6.  Engineer mode menu item descriptions: 

 

 
 

Item 

Mnemonic 

Description 

°C Type 

°F Type 

 

Step 

Default 

Range 

Default 

Range 

E1 

 

db 

Deadband offset 

2.0  

0~10.0 

7.0  

0~18.0 

0.5 (°C/°F) 

E2 

 

ESIC 

Unoccupied(ESI) Cooling Set 
Point 

28.0 

25.0~35.0 

82.0 

77.0~95.0 

1.0 (°C/°F)   

E3 

 

ESIH 

Unoccupied(ESI) Heating Set 
Point 

15.0 

10.0~22.0 

59.0  

50.0~72.0 

1.0 (°C/°F) 

E4 

 

I-t 

Integral Time and Output Cycle 
Time 

90 

10~500 

90 

10-500 

10 (Sec.) 

E5 

 

AO1L 

Not used 

 

 

 

 

 

E6 

 

AO1H 

Not used 

 

 

 

 

 

E7 

 

AO2L 

Analog Output 2 Low Adjustment 
(for FAN control) 

0~125 

0~125 

1(~0.044V) 

E8 

 

AO2H 

Analog Output 2 High 
Adjustment (for FAN control) 

-25 

-150~0 

-25 

-150~0 

1(~0.044V) 

E9 

 

SP-L 

Low Limit for Temperature Set 
Point 

10.0  

0~50.0 

50.0 

32.0~122.0  1.0 (°C/°F) 

E10   

SP-H 

High Limit for Temperature Set 
Point 

35.0  

0~50.0 

95.0 

32.0~122.0  1.0 (°C/°F) 

E11   

OFSt 

Current Temperature Offset 

0.0  

-10.0~10.0 

0.0 

-18.0~18.0  0.1 (°C/°F)   

E12   

Pb 

Proportional Band or Stage 
Width 

2.0  

0~10.0 

3.6 

0~18.0 

0.1 (°C/°F) 

E13   

LOC 

Bit Definition --- 

Bit 0: Mode Button 

  1: Down Buttons 

  2: Up Button  

  3: Fan Button 

  4: Power Button 

  5: Set Button  

    6: ESI Contact Detection 

  7:  Reserved 

 *Bit Value 

    0: Unlock / enable 

      1: Lock / disable  
 
Examples: 
0- Unlock/enable all 
1- Lock MODE Button                                 
2- Lock Down Button 
… 
8-Lock Fan Button 
… 
15-Lock MODE & Down & Up & 

Fan SPEED Buttons 

16-Lock Power Button 
… 
64-Disable ESI contact detection 
… 
… 
255- Lock/disable all 

0-255 

0-255 

 

 
                                                                                                                                           

 
 

 
 
 

 

Summary of Contents for TE226 Series

Page 1: ...et point temperature while it is flashing 8 Fan icons Indicate Fan status 9 Flake icon Indicate working in Cooling mode 10 Hot spring icon Indicate working in Heating mode 11 Flow icon Indicate workin...

Page 2: ...ntroller Mounting front cover 1 Lock front cover on the back plate by tightening the cover screw underneath with Philip screw driver Wiring Example 1 All wires must be inserted above the retainers of...

Page 3: ...splay Display Current Room or Set Point Temperature and Current Time Day Setting SP Parameter in Engineer Table to Choose Current Room or Set Point Temperature 2 Temperature Setting Set The Required T...

Page 4: ...Revised Date 2018 04 24 4 Fig 2 User Mode operation sequence...

Page 5: ...Revised Date 2018 04 24 5 Overview for the settings of Clock and Programmable Schedules Press MODE FAN or POWER button to escape any time during setting...

Page 6: ...Revised Date 2018 04 24 6 1 Detailed State Diagram for Clock Setting...

Page 7: ...for Schedule Setting Press Mode button to select day shows steadily deselect day flash Press MODE button to toggle Cooling Heating Set points Press MODE button to toggle Cooling Heating Set points Pre...

Page 8: ...8 00 16 0 8 00 16 0 Sch 3 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 18 00 21 0 Sch 4 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 22 00 16 0 l Unoccupied S...

Page 9: ...the LCD Stage On Current Temperature Cooling Stage Differential Dead Band Heating Stage Differential SP Cooling and Heating Control Auto Changeover Dead band Option 0 OFF Stage On Current Temperature...

Page 10: ...or delivery outside air from suite HRV or OA vent duct If there is a call for heating or cooling the fan would ramp up to maximum design airflow for the FCU on the project 3 Fan Mode By pressing FAN b...

Page 11: ...on the LCD c STOP mode means using manual S P instead of all Schedules i e Temporarily disable all programmable Schedules And the icon will be NOT shown on the LCD Examples of Engineering Mode 5 E19...

Page 12: ...ress UP or DOWN button to change the setting and press MODE button to confirm the setting and return to menu item selection For no button pressed for 10 seconds it will go back to menu item selection...

Page 13: ...Adjustment for FAN control 25 150 0 25 150 0 1 0 044V E9 SP L Low Limit for Temperature Set Point 10 0 0 50 0 50 0 32 0 122 0 1 0 C F E10 SP H High Limit for Temperature Set Point 35 0 0 50 0 95 0 32...

Page 14: ...lay SP E17 FAnL Lowest Fan Speed in Continuous Fan Mode 25 0 100 25 0 100 1 E18 Fan2 Medium Fan Speed 60 20 100 60 20 100 1 E19 dLAy Minimum delay time between cooling and heating 0 0 5 0 0 5 1 minute...

Reviews: